1. CONNECT REVO C/REVEX MODULE AND GP-
4116 screen
This part describes how to connect the power supply and communication cable to the REVO
C/REVEX. Also consult the CD Automation manual that was supplied with the REVO C/REVEX
module.
1.1 Connect communication cable between REVO C/REVEX
and GP4116.
You can connect the RS485 modbus communication cable between the REVO C M5 port and
the GP4116 COM1 connector.
REVO C:
M5 point 9=B and M1 point A+ (white wire to GP4116) and M1 point B- (brown wire to GP4116)
REVEX: different connections depending on the size of the thyristor
For 30-40A and 60-90A: use M3
For the larger thyristors, use M1 point 11-12