Download Print this page

Delta BX6.3_AC100 Quick Installation Manual page 2

Battery storage system

Advertisement

Installation
Insert Rawlplug
1. Drill 4 holes with Φ16 mm diameter in dimension 540 mm x 220 mm
2. Insert Rawlplug into these hole
3. Put on and fix BX6.3_AC100 firmly
CAUTION !
- Please do not install the battery
pack on uneven floor surfaces.
- Holes size is 16 mm diameter for
attaching the battery pack.
Wiring
Conduit hole(mm)
PF pipe(mm)
Φ34
Screw torque:
0.8 N·m
(8 kgf·cm)
* Please do not remove all the rubber covers on BX6.3_AC100 if BX6.3_EX100
is not installed.
Installation of BX12.6_AC100
① ② ③
Ground
540 mm
Φ28
① Uart signal
② Relay signal
③ Heater signal
Current Transformer installation
1. The CT can be opened.
2. Take the CT clip on the Line conductor wire.
3. please be aware of the CT direction.
Arrow symbol means utility grid.
4. Connect the CT wires to the device.
5. Connect CT wire to the CT port of
communication card.
Model
Enclosure
Operating temperature
Operating Altitude
Relative humidity
220 mm
Environmental category
Protection degree
Pollution degree
Overvoltage category
Galvanic isolation
Safety class
Weight
Dimensions(W*H*D)
Connectors
Audible noise
Type
Battery Module
Typical Energy
Typical Voltage
Voltage Range
Nominal power
Maximum power
Voltage
On Grid Nominal current
Stand-Alone Nominal current
Inrush current
Maximum output fault current (rms)
Maximum overcurrent protection
Frequency
Active anti-islanding method
Total harmonic distortion
Power factor
Output current DC component
Tare loss
Maximum efficiency
User interface
External communication
CE conformity
Grid interface
Emission
Harmonics
Variations and flicker
Immunity
Immunity
Electrical safety
* 0 degree for the first time installation.
CT label direction
BX6.3_AC100
GENERAL
Aluminum with powder coating
-10℃ * ~ 45℃
0 to 2000m (0 to 6666 ft.)
0% – 95% non-condensing.
Indoor / Outdoor
IP65 (Electronics)
PD 2
AC output :III
NO
Class I metal enclosure with protective earth
77kg
570 × 840 × 250 mm
Weather resistant connectors
< 40dB
BT INPUT
Li-ion
Samsung SDI 41J (21700)
6.3 kWh
DC 202.7 V
DC 175 - 228 V
AC INPUT / OUTPUT
3000 VA
3000 VA
According to country setting
(Programmable 230Vac ± 20%)
13 A
13 A
16 A / 100 us
25 A
25 A
Rated 50/60 Hz (Programmable 45-65 Hz)
Reactive power injection
< 3 %
> 0.99 @ full power
< 0.5% rated current
< 10 W
96.5%
SYSTEM INFORMATION / COMMUNICATION
Wi-Fi connection
365 days data logger and real time clock
30 events record
2 RS-485 connections
REGULATIONS & DIRECTIVES
Yes
AS/NZS 4777.2 :2015
EN 61000-6-3
EN 61000-3-2
EN 61000-3-3
EN 61000-6-2
ESD
IEC 61000-4-2
RS
IEC 61000-4-3
EFT
IEC 61000-4-4
Surge
IEC 61000-4-5
CS
IEC 61000-4-6
PFMF
IEC 61000-4-8
IEC 62619:2017, IEC 62040-1:2017
Energy meter
of the electric
utility
company
L
N
Main
Breaker
BX12.6_AC100
77 kg (BX6.3_AC)
+ 60 kg (BX6.3_EX)
570 × 840 × 250 mm
+ 520 × 600 × 230 mm
12.6 kWh
DC 405.4 V
DC 350 - 456 V
4500 VA
4500 VA
19.6 A
19.6 A
25 A
25 A
20210721

Advertisement

loading

This manual is also suitable for:

Bx12.6_ac100