Mitsubishi Electric Mr. Slim PKA Series Service Manual page 31

Hide thumbs Also See for Mr. Slim PKA Series:
Table of Contents

Advertisement

9-6. HOW TO CHECK THE PARTS
PKA-M35HA
PKA-M35HA-ER
Parts name
Room temperature
thermistor (TH1)
Pipe temperature
thermistor/liquid(TH2)
Condenser/evaporator
temperature thermistor (TH5)
Vane motor (MV)
2
RD
M
4
YE
1
BN
OG
GN
Connect pin No.
3
5
Fan motor (MF)
9-6-1. Thermistor
<Thermistor Characteristic Graph>
Thermistor for
lower temperature
Thermistor R
=15k" ± 3%
0
Fixed number of B=3480 ± 2%
1
Rt=15exp { 3480(
273+t
0:
15 k"
10:
9.6 k"
20:
6.3 k"
25:
5.4 k"
30:
4.3 k"
40:
3.0 k"
OCH660A
PKA-M50HA
PKA-M50HA-ER
Disconnect the connector then measure the resistance with a tester.
Refer to "9-6-1. Thermistor".
Measure the resistance between the terminals using a tester. (Coil temperature 25:)
1-2
1-3
Brown-Red
Brown-Orange
350" ± 7%
Refer to "9-6-2. DC Fan motor (fan motor/indoor controller circuit board)".
Room temperature thermistor (TH1)
Pipe temperature thermistor/liquid (TH2)
Condenser/evaporator temperature ther-
mistor (TH5)
1
) }
273
PKA-M35HAL
PKA-M35HAL-ER
Check points
Normal
1-4
1-5
Brown-Yellow
Brown-Green
31
PKA-M50HAL
PKA-M50HAL-ER
< Thermistor for lower temperature >
50
40
30
20
10
0
-20 -10 0
10 20 30 40 50
Temperature (:)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents