Lennox LIUH018021T431E-1 Service Manual page 113

Hide thumbs Also See for LIUH018021T431E-1:
Table of Contents

Advertisement

1.3.2.3 Evaporator Low Temperature T2 Protection.
---T2<0℃, the compressor stops and restarts only when T2≥5℃.
---0℃≤T2<4℃, the compressor frequency is limited and decreases to a lower level
---4℃≤T2<7℃, the compressor maintains its current frequency.
---T2>7℃, the compressor frequency is not limited.
1.3.2.4 High Condenser Coil Temperature Protection
T3
1.3.3 Heating Mode
1.3.3.1 Outdoor Fan Running Guidelines
12K
Fan speed is regulated according to T4 and compressor frequency.
Frequency linkage area:
Electrical Control System
T1-Td
a
b
c
d
e
12K
Off
Decrease
Hold
Increase slowly
Resume
T4
Frequency linkage area
A
A+
H
(H-L)*0.75+L
(H-L)*0.5+L
(H-L)*0.25+L
L
16~60K
T3
Off
Decrease
Hold
Resume