Electrical Data - Payne PG96VAT Installation, Start-Up, Operating And Service And Maintenance Instructions

Two-stage 4-way multipoise condensing gas furnace
Hide thumbs Also See for PG96VAT:
Table of Contents

Advertisement

UNIT
VOLTS---
OPERATING VOLTAGE
SIZE
HERTZ---
PHASE
Maximum*
30040
115--- 60--- 1
127
42060
115--- 60--- 1
127
48080
115--- 60--- 1
127
60080
115--- 60--- 1
127
1
60100
1
115--- 60--- 1
127
66120
115--- 60--- 1
127
1
* Permissible limits of the voltage range at which the unit operates satisfactorily.
# Unit ampacity = 125 percent of largest operating component's full load amps plus 100 percent of all other potential operating components' (EAC, humidifier,
etc.) full load amps.
Time ---delay type is recommended.
{
Length shown is as measured one way along wire path between furnace and service panel for maximum 2 percent voltage drop.
}
1
Low Amp Kit (KGAPC0101ECM) allows select furnaces to be installed with a 15 Amp Breaker and 14 AWG wire within the listed wire length. Affected data
shown as Default Value/Value with Lower Amp Kit.
Fig. 35 - - Installing J- -Box (When Used)
Table 11 – Electrical Data
TWO---STAGE PWM FURNACES
MAXIMUM
RANGE*
UNIT
AMPS
Minimum*
104
7.5
104
10.9
104
10.9
104
14.7/11.3
104
14.7/11.3
104
14.7/11.3
A12226
UNIT
MINIMUM
AMPACITY#
WIRE
SIZE
AWG
10.3
14
14.5
14
14.5
14
19.3/14.9
12/14
19.4/15.0
12/14
19.4/15.0
12/14
GROUND
NEUTRAL
LINE VOLTAGE
ELECTRIC
DISCONNECT
SWITCH
Fig. 36 - - Field- -Supplied External Electrical Box on Furnace
36
MAXIMUM
MAXIMUM
WIRE LENGTH
FUSE OR CKT
FT (M)}
BKR
AMPS{
36
(10.9)
25
(7.6)
25
(7.6)
29/24
(8.8/7.3)
20/15
29/24
(8.8/7.3)
20/15
29/24
(8.8/7.3)
20/15
COPPER
WIRE ONLY
ALUMINUM
WIRE
Casing
15
15
15
A11146