14.3 Outdoor Fan Motor Operation
It starts when compressor starts operation and it stops 30 seconds after compressor stops operation.
During cooling operation, and outdoor ambient temperature is below 8°C, outdoor fan speed will be controlled
according to outdoor piping temperature as following:
During above condition, when indoor heat exchanger temperature is below 5°C, the outdoor fan will stop
according to outdoor piping temperature as following:
OD Pipe Temperature
A
25°C
B
28°C
58