Periodic inspection
To maintain the full performance of Rabbit Portable Fire Fighting Pump, please take a periodic
inspection by the certified mechanic for portable fire fighting pump maintenance every six
months.
Some parts used for the portable fire pump deteriorates its function due to the time
degradation, even if you cannot find the problem on the surface. Make sure to replace such
a part referring to the below chart in taking the periodic inspection.
● Periodic replacement parts
Vacuum pump driving V belt
● Periodic replacement items
Periodic replacement items
Name of part
Spark Plug
Fuel Pipe
Battery
Oil Pipe
Oil Filter
Other rubber parts
Fuel
Governor Oil
Estimated time for replacement
Every year
Every 2 years
Every 2 years
Every 3 years
Every 3 years
Every 3 years
Every 2 years
Estimated time for replacement
Every 6 months
Operation time: 50 hours/year