Configuration Continued
Beacon Flash Rate (Set on Beacon)
Switch 2 on the two way switch is used to
configure the beacon flash rate. Switch 1 is
not used on this product.
Default setting: 1Hz Flash Rate
Audio Monitoring (Set on Wireless Module)
The device has an audio self test feature which
is not used on this version of product.
Both switches should be OFF as shown.
Default setting: Audio Monitoring Disabled
Specification
Operating
Temperature
-10°C to 55°C
Storage
Temperature
5°C to 30°C
Humidity
Up to 95% non-condensing
Supply
3x AA Alkaline (Panasonic LR6AD Powerline / Varta
4006 Industrial) 3x C Alkaline (Panasonic LR14AD
Powerline / Varta 4014 Industrial)
CAUTION!
Fitting of an incorrect battery type invalidates the product certification and
may result in poor performance.
IP Rating
IP54
Operating
Frequency
868MHz
Output
Transmitter
Power
Auto adjusting 0 - 14 dBm (0 - 25 mW)
Beacon Element
Voltage
17-60Vdc Operating at 18Vdc
Beacon Element
Max Current
40mA @ 1Hz flash rate
Flash Rate
0.5Hz/1Hz (selectable)
Beacon
Coverage
C-3-15 (Ceiling mounted variant) / W-3.1-11.3
(Wall mounted variant)
Dimensions
120mm (Ø) 145mm (D)
Weight
0.65kg
Location
Type A: For indoor use
www.acornfiresecurity.com
SWITCH 1 = NOT USED
SWITCHES 1 & 2 = NOT USED
www.acornfiresecurity.com
Page 2 of 2
FLASH
SWITCH
2
RATE
ON
1Hz
2
1
2
0.5Hz
OFF
2
1
2
2
Regulatory Information
Manufacturer
EMS Security Group Ltd. Technology House, Herne
Bay, Kent, CT6 8JZ, United Kingdom
Year of
manufacture
See devices serial number label
14
Certification
0359
Certification
body
CPR Certificate
DOP
0359-CPR-00292
Approved to
See part listing for associated products:
EN54-23:2010. Fire detection and fire alarm
systems. Part 23: Fire alarm devices. Visual alarm
devices.
EN54-25:2008.
September 2010 and March 2012. Fire detection
and fire alarm systems.
Part 25: Components using radio links.
European
EMS Security Group Ltd hereby declares that this
Union
device
requirements and other relevant provisions of
Directive 2014/53/EU (R&TTE directive).
2012/19/EU (WEEE directive):
Products marked with this symbol cannot be
disposed of as unsorted municipal waste in the
European Union. For proper recycling, return this
product to your local supplier upon purchase of
equivalent new equipment, or dispose of it at
designated collection points. For more information
see www.recyclethis.info
Dispose of your batteries in an environmentally
friendly manner according to your local regulations.
Beacon
ON
1
2
www.emsgroup.co.uk
Wireless Module
IDENT
PRESS HERE TO
LOG ON
[1]
Incorporating
corrigenda
[2]
is
in
compliance
with
the
essential

Advertisement

loading

This manual is also suitable for:

Fc-171-002Fc-323-ca1Fc-323-ca2Fc-323-wa1Fc-323-wa2