ADLI V2 FO
Addressable Loop Interface
INSTALLATION / PROGRAMMING MANUAL

GENERAL DESCRIPTION

The ADLI FO V2 is an addressable loop fibre optic interface which allows a conventional ORION / ORION-EX V2
panel to be integrated in any of GFE's analogue addressable systems, allowing the addressable panel to monitor
and control the status of the conventional panel. An 8 way DIL switch is provided to set the module's address and to
configure the advanced features.
There are two assemblies of the ADLI V2 FO: ​ A DLI V2 FO LOOP and ​ A DLI V2 FO ORION​ . Every ORION / ORION-EX V2
panel has to be equipped with one ADLI V2 FO ORION and every link that connects to the loop has to be equipped with one
ADLI V2 FO LOOP.

MAIN FEATURES

● Fast activation response
● Three status LEDs
● Remote sound / Silence alarms
● Remote reset
● Low power consumption
● Automatic conventional panel recognition
● Fault and fire status report
● Different analogue values for zone, panel and supply faults for easier troubleshooting
● Programmable number of addresses to report (for ORION conventional panel)
● Programmable extinguishing, pre-release delay, sounder and disablements status report
using 4 additional addresses reporting as I/Os (ORION-EX V2 panel only)

IMPORTANT SAFETY NOTES

● This equipment must only be installed and maintained by a suitably qualified and technically competent person.
● A basic knowledge and training in the installation of Fire and Extinguish Detection systems is assumed.
● The fire detection system should be designed by a suitably qualified person with reference to the local Regulations
and Guidance from the Fire Officer where applicable.
www.acornfiresecurity.com
www.acornfiresecurity.com
ma_adlifo_01_020000_en_200714
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ADLI V2 FO and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Global Fire Equipment ADLI V2 FO

  • Page 1 There are two assemblies of the ADLI V2 FO: ​ A DLI V2 FO LOOP and ​ A DLI V2 FO ORION​ . Every ORION / ORION-EX V2 panel has to be equipped with one ADLI V2 FO ORION and every link that connects to the loop has to be equipped with one ADLI V2 FO LOOP.
  • Page 2 Global Fire Equipment // ​ g lobalfire.pt ma_adlifo_01_020000_en_200714 COMPATIBILITY NOTE ADLI V2 FO ​ m odule is only compatible with ​ O RION / ORION-EX V2​ panels that exhibit the following sequential LED pattern during RESET: ORION ​ L ED pattern ORION-EX V2 ​...
  • Page 3 REPORTED ANALOGUE VALUES The ADLI V2 FO reports different analogue values depending on the status and type of fault present on the conventional panel, allowing a faster troubleshooting. The table below describes the different analogue values reported to the addressable panel.
  • Page 4 If connected to an ORION conventional panel, the ADLI V2 FO assumes only one address, by default, but can be configured to assume one address per zone. If it is configured to have one address per zone, the ADLI V2 FO will assume 2 / 4 / 8 consecutive addresses, starting from the address that is set on the D.I.L.
  • Page 5 Global Fire Equipment // ​ g lobalfire.pt ma_adlifo_01_020000_en_200714 www.acornfiresecurity.com...
  • Page 6 If the ADLI V2 FO is configured to report with ​ 2 / 4 / 8 ADDRESSES​ , it will assume 2 / 4 / 8 consecutive addresses on the loop (​...
  • Page 7 Global Fire Equipment // ​ g lobalfire.pt ma_adlifo_01_020000_en_200714 I/O REPORT ​ This configuration will only have effect when the ADLI V2 FO is to be used with an ORION-EX V2 NOTE: Conventional Extinguishing Panel. This programmable feature allows the user to configure the ADLI V2 FO to report the state of ORION-EX V2’s S1 sounder, Pre-release delay, REM and general disablement LED​...
  • Page 8 NUMBER OF ADDRESSES TO REPORT FUNCTION Let's assume that the ADLI V2 FO is to be used with an ORION Conventional Fire Detection Panel with 8 fire detection zones, and the desired configuration is to report one address per zone.

This manual is also suitable for:

Adli v2

Table of Contents