Event codes

Technical data

42
Code
Meaning
Module related event codes
E10
Module fault
E13
Events from the overflow matrix register
E50
Module reset
E51
Event register overflow
Channel related event codes
E1
Alarm channel active
E2
Alarm channel reset
E3
Alarm channel active, signal follower, no blink- or audible functionality
E4
Alarm channel reset, signal follower
Alarm channels
Number of alarm channels
Type of field contact signal
Internally generated field contact voltage
Loop current of closed field contact circuit
Channel input and reset delay time, field-selectable
Max. counting frequency for pulse counter
*) = factory settings
External acknowledge/reset inputs
Channel acknowledge/ reset
Reset of audible device
The control voltage for the acknowledge/reset
circuits is taken from the internal supply
Reflash signal outputs
Fixed reflash group alarm outputs
Audible device output
Internal self-supervision output
Output relay contact types
Additional group alarm or signal following outputs
Rated contact current/breaking voltage
Breaking capacity for dc currents when
the load time-constant L/ R < 40 ms at
the voltage levels 48/110/220 V dc
16 channels
Normally open contact *)
Normally closed contact
Raising and/or falling edge
Pulse counter
48 V dc + 20 %
4 mA ±20%
5 ms, 20 ms * ), 100 ms,
1 s, 5 s, 20 s, 60 s or 160 s
Other values possible over
the serial communication
3 Hz
Closing contact
Closing contact
48 V dc + 20 %
2 relays
1 relay
1 relay
Normally open contacts, changeable
to normally closed contacts
16 relays (NO, not possible to change)
3 A/250 V ac or dc
1 A/0.25 A/0.15 A