Programming

Programming
technique
28
The alarm annunciator unit is a very flexible
device but at the same time easy to use.
The programming work is carried out easily by
means of the programming push-buttons on the
front panel or via the serial communication
using e.g. the SMS 010 setting and monitoring
software. The parameter values are stored in a
non-volatile EEPROM memory which means
that the parameter programming is a very straight
forward action and that the information con-
tent of the memory is maintained even in a loss
of supply situation.
The annunciator unit is programmed by means
of the five push-buttons and the four digit
display on the front panel. The push-buttons are
FAULT
ON
Fig. 29. Front view of the annunciator unit.
The parameter values can be and are usually
finally defined after that the annunciator unit
has been mounted at site during the commis-
sioning work.
By means of a plug selector located on the PCB
just behind the front panel the switching over of
the annunciator unit into the programming
mode can be prohibited. In this way the pro-
gram memory of the annunciator unit can be
protected against unauthorized access.
accessible after that the plastic lid has been
opened.
Four-digit seven-segment display
Enter command push-button
Parameter pointer indicators
Parameter selector push-button
Data value selector push-button
Display cursor control push-button
Channel selector push-button