Module related
parameters
Selection of mode
of operation for
the reflash output
relays
32
The programming examples and selections above
have all been channel specific which means that
the parameters are selected individually for each
channel.
The LED marked OUTPUT is called up with
the parameter selector push-button ↓ and the
first two digits from the left of the display are
activated with the cursor control push-button
→. The blinking digits indicate, as listed below,
which reflash group is being programmed at the
moment, i.e.:
01 = output reflash group 1
02 = output reflash group 2
-
-
-
16 = output reflash group 16
The reflash group in question is called up with
the data value selector push-button ↑, after
which the cursor is moved to digits three and
four from the left of the display with the cursor
control push-button →. The two digits are
The function which will be described in the
following section is annunciator specific, which
means that the selected function concerns the
whole annunciator unit.
indicating the mode of reflash alarm signal for
the selected output reflash group as follows:
0 = field contact following reflash (FCFR)
1 = acknowledge action controlled reflash
(AACR)
2 = impulse shaping reflash (ISR), impulse
length 300 ms
3 = field contact following reflash with a 300 ms
interruption of the reflash signal any time a
new alarm signal joins into an already active
group alarm
4 = FCFR + AACR, Field Contact Following
Reflash and Action Controlled Reflash
Se figure on page 13.
The chosen reflash mode is selected with the
data value selector push-button ↑ and stored in
the parameter memory with the enter command
push-button.