COMMERCIAL CONDENSING UNITS
COMMERCIAL CONDENSING UNITS
TECHNICAL MANUAL
DIGITAL SINGLE SCROLL
Variable Capacity
Variable Capacity
Medium Temperature Applications
Medium Temperature Applications
Medium Temperature Applications
ISSUE: 01.08.2020
SCROLL

Advertisement

Table of Contents
loading

Summary of Contents for J&E Hall JEHSD-0400-B3-M-3

  • Page 1 COMMERCIAL CONDENSING UNITS COMMERCIAL CONDENSING UNITS TECHNICAL MANUAL V3 DIGITAL DIGITAL SINGLE SCROLL SCROLL Commercial Condensing Units Commercial Condensing Units Commercial Condensing Units Variable Capacity Variable Capacity Medium Temperature Applications Medium Temperature Applications Medium Temperature Applications ISSUE: 01.08.2020...
  • Page 2: Table Of Contents

    Contents Nomenclature Standard Product Configuration Specifications 4-11 Health & Safety Installation 13-16 Commissioning 17-26 Control Logic 27-28 Alarm Information 29-30 Dimensional Drawings Electrical Wiring Diagrams 32-33 Service & Maintenance 34-35 F-Gas Information Technical Information 37-40 Certification 41-43 Issue: 01.08.2020 Page 2...
  • Page 3: Nomenclature

    Nomenclature JEH SD 0400 B 3 M 3 ① ② ③ ④ ⑤ ⑥ ⑦ ① J & E Hall International ⑤ Unit Series ② SD: Digital Scroll ⑥ M: Medium Temperature L: Low Temperature ③ Approximate HP (0400 = 4.0hp) ⑦...
  • Page 4 Volume Receiver Unit Model Swept Charge Weight Liquid Suction Volume Charge Type (m³/h) (Litres) (Litres) (Litres) (Litres) (m³/h) (inch) (inch) (kgs) dB(A) JEHSD-0400-B3-M-3 ZBD29KQE-TFD 11.40 1.36 10.8 4.42 4250 JEHSD-0600-B3-M-3 ZBD45KQE-TFD 17.10 1.89 13.5 74.0 6.89 4100 JEHSD-0800-B4-M-3 ZBD57KCE-TFD 22.10 1.89...
  • Page 5: Specifications

    Specifications SEPR Data SEPR (10K SH) Unit Model JEHSD-0400-B3-M-3 3.26 3.23 3.15 3.15 JEHSD-0600-B3-M-3 3.24 3.08 2.93 2.93 JEHSD-0800-B4-M-3 2.75 2.84 2.75 2.75 SEPR (20 C RGT) Unit Model JEHSD-0400-B3-M-3 3.31 3.25 3.20 3.20 JEHSD-0600-B3-M-3 3.30 3.10 2.98 2.98 JEHSD-0800-B4-M-3 2.81...
  • Page 6 9380 11250 6440 2770 2870 2970 3070 3160 3240 1.52 1.84 2.17 2.54 2.97 3.47 5030 6160 7480 9040 10900 JEHSD-0400-B3-M-3 4.00 3050 3160 3250 3340 3400 1.65 1.95 2.30 2.71 3.21 4790 5880 7150 8680 10550 3250 3360 3450...
  • Page 7 5660 8350 10050 12150 6910 3150 3260 3350 3430 3490 1.80 2.12 2.49 2.93 3.48 5400 6600 8000 9670 11650 JEHSD-0400-B3-M-3 4.00 3360 3470 3570 3650 3700 1.61 1.90 2.24 2.65 3.15 6290 7640 9250 11200 3700 3800 3880 3930 1.70...
  • Page 8 2860 3060 3260 3450 3630 3810 1.64 1.85 2.08 2.33 2.61 2.92 3.27 4130 5060 6110 7300 8660 10250 12000 JEHSD-0400-B3-M-3 4.00 2720 2980 3210 3420 3620 3800 3980 1.52 1.70 1.90 2.13 2.39 2.70 3.02 3940 4830 5840 6980...
  • Page 9 2.63 3.04 3.48 3.97 7960 9520 11350 6620 2970 3070 3160 3240 2.23 2.59 3.01 3.50 6360 7660 9180 11000 JEHSD-0400-B3-M-3 4.00 3160 3250 3340 3400 2.01 2.36 2.75 3.24 7350 8840 10650 3450 3530 3570 2.13 2.50 2.98 6830...
  • Page 10 2.54 2.95 3.43 4.02 8460 10150 12200 7030 3260 3350 3430 3490 2.16 2.53 2.96 3.50 6740 8130 9760 11700 JEHSD-0400-B3-M-3 4.00 3470 3570 3650 3700 1.94 2.28 2.67 3.16 7780 9360 11250 3800 3880 3930 2.05 2.41 2.86 8690 4290 2.03...
  • Page 11 2630 2860 3060 3260 3450 3630 3810 1.72 1.92 2.15 2.39 2.66 2.95 3.27 5290 6340 7510 8830 10350 12000 JEHSD-0400-B3-M-3 4.00 2980 3210 3420 3620 3800 3980 1.78 1.98 2.20 2.44 2.72 3.02 5080 6080 7210 8480 9930 11600...
  • Page 12: Health & Safety

    Health and Safety Important Note: Only qualified personnel, who are familiar with refrigeration systems and components including all controls, should perform the installation and start-up of the system. To avoid potential injury, use care when working around coil surfaces or sharp edges of metal cabinets. All piping and electrical wiring should be installed in accordance with all applicable standards and local by-laws.
  • Page 13: Installation

    Installation Unit location In order to achieve maximum cooling capacity, the installation location for the condensing unit should be carefully selected. • Install the condensing unit in such a way so that hot air ejected by the condensing unit cannot be drawn in again (short circuit •...
  • Page 14 Installation Field piping Important Note: Pipe sizing should only be determined by qualified personnel. Correct line sizing will minimize the pressure drop and maintain sufficient gas velocity for proper oil return. All applicable standards must be observed in the installation of refrigerant piping. To ensure satisfactory operation and performance, the following points should be noted: Pipework routes must be as simple and as short as possible.
  • Page 15 Installation Pressure testing The condensing units are pressure tested in the factory prior to dispatch. All units come with a holding charge of oxygen free nitrogen. Remove the holding charge indication tag which is tied to service valve before installation. Once the pipework installation is complete, it should be pressure tested prior to evacuation to test for leaks.
  • Page 16 Installation Electrical Important Note: The mains electrical supply to the condensing unit must be via a suitable motor rated circuit breaker or fuse. A mains isolator is fitted to all condensing units therefore an additional isolator is not required unless site conditions or regulations dictate differently.
  • Page 17: Commissioning

    Commissioning Access to Controller and LCD Display Access to Controller and LCD Display Important Note: Warning! Only Authorized personnel are allowed to access the Warning! Only Authorized personnel are allowed to access the Warning! Only Authorized personnel are allowed to access the controller and LCD display.
  • Page 18 Commissioning Pre startup checks Before starting the condensing unit the following checks should be carried out as a minimum: • Check electrical supply is correct and all connections are sound. • All moving parts are free and guards fitted. • Compressor oil level satisfactory. •...
  • Page 19 Commissioning The User Terminal Interface – LCD Display The user terminal can be used to perform all the operations allowed by the program, display the operating conditions of the unit at all times, and set the parameters. It can be disconnected from the main board, and in fact is not required for operation. Button Functions ALARM Displays the alarms...
  • Page 20 Commissioning Controller Home Screen Following controller power-up and initialisation process (approximately 1 minute), the controller home screen will appear as up and initialisation process (approximately 1 minute), the controller home screen will appear as up and initialisation process (approximately 1 minute), the controller home screen will appear as follows: The low pressure and high pressure conditions of the unit are displayed.
  • Page 21 Commissioning Changing Set Point & Refrigerant Selection Changing Set Point & Refrigerant Selection 1. With controller Home screen displayed, Press PRG button to go Main Menu screen and select “B. Setpoint” With controller Home screen displayed, Press PRG button to go Main Menu screen and select “B. Setpoint” With controller Home screen displayed, Press PRG button to go Main Menu screen and select “B.
  • Page 22 Commissioning Switch Unit ON / OFF (By Controller) Switch Unit ON / OFF (By Controller) 1. With controller Home screen displayed, Press PRG button to go Main Menu screen and select “A. On/Off Unit” displayed, Press PRG button to go Main Menu screen and select “A. On/Off Unit” displayed, Press PRG button to go Main Menu screen and select “A.
  • Page 23 Commissioning Altering Low Pressure Alarm Notification Setting Low Pressure Alarm Notification Setting (Optional) 1. With controller Home screen displayed, Press PRG button to go Main Menu screen and select “ With controller Home screen displayed, Press PRG button to go Main Menu screen and select “ With controller Home screen displayed, Press PRG button to go Main Menu screen and select “B.Setpoint”...
  • Page 24 Commissioning Compressor Operation The compressor(s) operate in accordance to the suction pressure setpoint which is programmed into the controller. There is a differential pressure setting both above and below the setpoint. This allows stable operation of the compressors without constantly switching on & off due to small variations in suction pressure. This range is known as the Neutral Zone.
  • Page 25 Commissioning Safety pressure switch settings (Mechanical) The Saginomiya SNS low pressure switch fitted to the JEH Digital Scroll condensing unit has adjustable cut-out and differential. High pressure protection is provided by a cartridge type high pressure switch (HP1) which has fixed settings. High Pressure Safety The high pressure safety switch is required to stop the compressor should the discharge pressure exceed the values shown in the following table.
  • Page 26 Commissioning AC Fan Speed Modulation Controller AC Fan Speed Modulation Controller (cont’d) Recommended settings to gain higher energy efficiency as published in the Ecodesign data sheets are as follows: Recommended settings to gain higher energy efficiency as published in the Ecodesign data sheets are as follows: Recommended settings to gain higher energy efficiency as published in the Ecodesign data sheets are as follows: •...
  • Page 27: Control Logic

    Control Logic Parameters for neutral zone compressor control Parameters for neutral zone compressor control 1. Preset differentials for neutral zone, activation Preset differentials for neutral zone, activation zone and deactivation zone. zone and deactivation zone. Neutral zone The operating principle is schematized in the above figure: The operating principle is schematized in the above figure: Inside the neutral zone the capacity request sent by the controller is constant (except when there is a modulation device and Inside the neutral zone the capacity request sent by the controller is constant (except when there is a modulation device and...
  • Page 28 Control Logic Parameters for neutral zone compressor control Parameters for neutral zone compressor control As well as the decrease and increase differentials, 4 time As well as the decrease and increase differentials, 4 time parameters are preset, two for each zone, which represent the parameters are preset, two for each zone, which represent the maximum and minimum time to reach the request, equal to 0% or 100%, for the decrease and increase respectively.
  • Page 29: Alarm Information

    Alarm Information Alarm Settings 1. Low pressure alarm (by transducer) 2. High pressure alarm (by transducer) 3. High condensing coil temperature alarm High condensing coil temperature alarm 4. High discharge alarm for fixed scroll compressor (if applicable) High discharge alarm for fixed scroll compressor (if applicable) Issue: 01.08.2020 Page 29...
  • Page 30 Alarm Information Alarm Settings The alarms below are in ascending order of priority. When there is any alarm, the alarm code will be displayed on the main sc The alarms below are in ascending order of priority. When there is any alarm, the alarm code will be displayed on the main sc The alarms below are in ascending order of priority.
  • Page 31: Dimensional Drawings

    Dimensional Drawings JEHSD-0400-B3-M-3, JEHSD-0600-B3-M-3 JEHSD-0800-B4-M-3 Issue: 01.08.2020 Page 31...
  • Page 32: Electrical Wiring Diagrams

    Electrical Wiring Diagram JEHSD-0400-B3-M-3, JEHSD-0600-B3-M-3 Issue: 01.08.2020 Page 32...
  • Page 33 Electrical Wiring Diagram JEHSD-0800-B4-M-3 Issue: 01.08.2020 Page 33...
  • Page 34: Service & Maintenance

    Service & Maintenance Important Note: Warning! – Disconnect the mains electrical supply before servicing or opening the unit. The condensing units are designed to give long life operation with minimum maintenance. However, they should be routinely checked and the following service schedule is recommended under normal circumstances: The removal of the top, side and front panels ensures that all parts are accessible.
  • Page 35 Tightening Torque Toghtening Torque Ball Valve Liquid Suction Hose and HL (Nm) (Nm) Pressure Switch Main Cap Main Cap Hexagonal Cap Main Cap JEHSD-0400-B3-M-3 ZBD29KQE-TFD Not Applicable M18*1.0mm M33*1.5mm M16*1.0mm (Brazed Connection) (25-30 Nm) (42-47Nm) (10-15Nm) 7/16" - 20UNF JEHSD-0600-B3-M-3 ZBD45KQE-TFD (14-16 Nm) 1-1/4"-12UNF...
  • Page 36: F-Gas Information

    F-Gas Information From 1/1/2015, F-Gas Regulation EU 517/2014 came into force replacing the old Regulation EC 842/2006. This affects system labelling, information supplied within documentation and also the way in which thresholds for frequency of leak testing refrigeration systems are calculated. Please be aware of the following: The models of equipment covered in this Technical Manual rely on fluorinated greenhouse gases for their functioning.
  • Page 37: Technical Information

    Technical Information Dual Pressure Switch Safety pressure switch settings: The pressure switch fitted to condensing units with auto reset for low pressure is factory preset to 1.0 bar cut-out. Do not set pressure control below this setting. Setting procedure for Low Pressure switch Range: Turning the range adjusting screw (2) clockwise will decrease the cut-in pressure setting.
  • Page 38 Technical Information Small Version Controller Please Note: The battery in the controller should be changed every three years. Issue: 01.08.2020 Page 38...
  • Page 39 Technical Information Small Version Controller Issue: 01.08.2020 Page 39...
  • Page 40 Technical Information Oil Separator Technical Data Operating Medium R407A/R407F/R448A/R449A Design Pressure, DP (MPa) Design Temperature, TS ( -40 ~ 130 Maximum Allowable pressure (MPa) Weight (kg) Marking Connection Volume Initial Oil Charge Type Part No. Category Litres Litres RSPW 55855 5/8‘‘...
  • Page 41: Certification

    Certification Issue: 01.08.2020 Page 41...
  • Page 42 Certification Issue: 01.08.2020 Page 42...
  • Page 43 Certification Issue: 01.08.2020 Page 43...
  • Page 44 J & E Hall Limited Hansard Gate West Meadows Derby, DE21 6JN England Tel: + 44 (0) 1332 253400 Fax: + 44 (0) 1332 371061 Email: helpline@jehall.co.uk www.jehall.com Issue: 01.08.2020 Issue: 01.08.2020 Page 44...