COMMERCIAL CONDENSING UNITS COMMERCIAL CONDENSING UNITS TECHNICAL MANUAL V3 DIGITAL DIGITAL SINGLE SCROLL SCROLL Commercial Condensing Units Commercial Condensing Units Commercial Condensing Units Variable Capacity Variable Capacity Medium Temperature Applications Medium Temperature Applications Medium Temperature Applications ISSUE: 01.08.2020...
Nomenclature JEH SD 0400 B 3 M 3 ① ② ③ ④ ⑤ ⑥ ⑦ ① J & E Hall International ⑤ Unit Series ② SD: Digital Scroll ⑥ M: Medium Temperature L: Low Temperature ③ Approximate HP (0400 = 4.0hp) ⑦...
Health and Safety Important Note: Only qualified personnel, who are familiar with refrigeration systems and components including all controls, should perform the installation and start-up of the system. To avoid potential injury, use care when working around coil surfaces or sharp edges of metal cabinets. All piping and electrical wiring should be installed in accordance with all applicable standards and local by-laws.
Installation Unit location In order to achieve maximum cooling capacity, the installation location for the condensing unit should be carefully selected. • Install the condensing unit in such a way so that hot air ejected by the condensing unit cannot be drawn in again (short circuit •...
Page 14
Installation Field piping Important Note: Pipe sizing should only be determined by qualified personnel. Correct line sizing will minimize the pressure drop and maintain sufficient gas velocity for proper oil return. All applicable standards must be observed in the installation of refrigerant piping. To ensure satisfactory operation and performance, the following points should be noted: Pipework routes must be as simple and as short as possible.
Page 15
Installation Pressure testing The condensing units are pressure tested in the factory prior to dispatch. All units come with a holding charge of oxygen free nitrogen. Remove the holding charge indication tag which is tied to service valve before installation. Once the pipework installation is complete, it should be pressure tested prior to evacuation to test for leaks.
Page 16
Installation Electrical Important Note: The mains electrical supply to the condensing unit must be via a suitable motor rated circuit breaker or fuse. A mains isolator is fitted to all condensing units therefore an additional isolator is not required unless site conditions or regulations dictate differently.
Commissioning Access to Controller and LCD Display Access to Controller and LCD Display Important Note: Warning! Only Authorized personnel are allowed to access the Warning! Only Authorized personnel are allowed to access the Warning! Only Authorized personnel are allowed to access the controller and LCD display.
Page 18
Commissioning Pre startup checks Before starting the condensing unit the following checks should be carried out as a minimum: • Check electrical supply is correct and all connections are sound. • All moving parts are free and guards fitted. • Compressor oil level satisfactory. •...
Page 19
Commissioning The User Terminal Interface – LCD Display The user terminal can be used to perform all the operations allowed by the program, display the operating conditions of the unit at all times, and set the parameters. It can be disconnected from the main board, and in fact is not required for operation. Button Functions ALARM Displays the alarms...
Page 20
Commissioning Controller Home Screen Following controller power-up and initialisation process (approximately 1 minute), the controller home screen will appear as up and initialisation process (approximately 1 minute), the controller home screen will appear as up and initialisation process (approximately 1 minute), the controller home screen will appear as follows: The low pressure and high pressure conditions of the unit are displayed.
Page 21
Commissioning Changing Set Point & Refrigerant Selection Changing Set Point & Refrigerant Selection 1. With controller Home screen displayed, Press PRG button to go Main Menu screen and select “B. Setpoint” With controller Home screen displayed, Press PRG button to go Main Menu screen and select “B. Setpoint” With controller Home screen displayed, Press PRG button to go Main Menu screen and select “B.
Page 22
Commissioning Switch Unit ON / OFF (By Controller) Switch Unit ON / OFF (By Controller) 1. With controller Home screen displayed, Press PRG button to go Main Menu screen and select “A. On/Off Unit” displayed, Press PRG button to go Main Menu screen and select “A. On/Off Unit” displayed, Press PRG button to go Main Menu screen and select “A.
Page 23
Commissioning Altering Low Pressure Alarm Notification Setting Low Pressure Alarm Notification Setting (Optional) 1. With controller Home screen displayed, Press PRG button to go Main Menu screen and select “ With controller Home screen displayed, Press PRG button to go Main Menu screen and select “ With controller Home screen displayed, Press PRG button to go Main Menu screen and select “B.Setpoint”...
Page 24
Commissioning Compressor Operation The compressor(s) operate in accordance to the suction pressure setpoint which is programmed into the controller. There is a differential pressure setting both above and below the setpoint. This allows stable operation of the compressors without constantly switching on & off due to small variations in suction pressure. This range is known as the Neutral Zone.
Page 25
Commissioning Safety pressure switch settings (Mechanical) The Saginomiya SNS low pressure switch fitted to the JEH Digital Scroll condensing unit has adjustable cut-out and differential. High pressure protection is provided by a cartridge type high pressure switch (HP1) which has fixed settings. High Pressure Safety The high pressure safety switch is required to stop the compressor should the discharge pressure exceed the values shown in the following table.
Page 26
Commissioning AC Fan Speed Modulation Controller AC Fan Speed Modulation Controller (cont’d) Recommended settings to gain higher energy efficiency as published in the Ecodesign data sheets are as follows: Recommended settings to gain higher energy efficiency as published in the Ecodesign data sheets are as follows: Recommended settings to gain higher energy efficiency as published in the Ecodesign data sheets are as follows: •...
Control Logic Parameters for neutral zone compressor control Parameters for neutral zone compressor control 1. Preset differentials for neutral zone, activation Preset differentials for neutral zone, activation zone and deactivation zone. zone and deactivation zone. Neutral zone The operating principle is schematized in the above figure: The operating principle is schematized in the above figure: Inside the neutral zone the capacity request sent by the controller is constant (except when there is a modulation device and Inside the neutral zone the capacity request sent by the controller is constant (except when there is a modulation device and...
Page 28
Control Logic Parameters for neutral zone compressor control Parameters for neutral zone compressor control As well as the decrease and increase differentials, 4 time As well as the decrease and increase differentials, 4 time parameters are preset, two for each zone, which represent the parameters are preset, two for each zone, which represent the maximum and minimum time to reach the request, equal to 0% or 100%, for the decrease and increase respectively.
Alarm Information Alarm Settings 1. Low pressure alarm (by transducer) 2. High pressure alarm (by transducer) 3. High condensing coil temperature alarm High condensing coil temperature alarm 4. High discharge alarm for fixed scroll compressor (if applicable) High discharge alarm for fixed scroll compressor (if applicable) Issue: 01.08.2020 Page 29...
Page 30
Alarm Information Alarm Settings The alarms below are in ascending order of priority. When there is any alarm, the alarm code will be displayed on the main sc The alarms below are in ascending order of priority. When there is any alarm, the alarm code will be displayed on the main sc The alarms below are in ascending order of priority.
Service & Maintenance Important Note: Warning! – Disconnect the mains electrical supply before servicing or opening the unit. The condensing units are designed to give long life operation with minimum maintenance. However, they should be routinely checked and the following service schedule is recommended under normal circumstances: The removal of the top, side and front panels ensures that all parts are accessible.
Page 35
Tightening Torque Toghtening Torque Ball Valve Liquid Suction Hose and HL (Nm) (Nm) Pressure Switch Main Cap Main Cap Hexagonal Cap Main Cap JEHSD-0400-B3-M-3 ZBD29KQE-TFD Not Applicable M18*1.0mm M33*1.5mm M16*1.0mm (Brazed Connection) (25-30 Nm) (42-47Nm) (10-15Nm) 7/16" - 20UNF JEHSD-0600-B3-M-3 ZBD45KQE-TFD (14-16 Nm) 1-1/4"-12UNF...
F-Gas Information From 1/1/2015, F-Gas Regulation EU 517/2014 came into force replacing the old Regulation EC 842/2006. This affects system labelling, information supplied within documentation and also the way in which thresholds for frequency of leak testing refrigeration systems are calculated. Please be aware of the following: The models of equipment covered in this Technical Manual rely on fluorinated greenhouse gases for their functioning.
Technical Information Dual Pressure Switch Safety pressure switch settings: The pressure switch fitted to condensing units with auto reset for low pressure is factory preset to 1.0 bar cut-out. Do not set pressure control below this setting. Setting procedure for Low Pressure switch Range: Turning the range adjusting screw (2) clockwise will decrease the cut-in pressure setting.
Page 38
Technical Information Small Version Controller Please Note: The battery in the controller should be changed every three years. Issue: 01.08.2020 Page 38...
Page 39
Technical Information Small Version Controller Issue: 01.08.2020 Page 39...
Page 40
Technical Information Oil Separator Technical Data Operating Medium R407A/R407F/R448A/R449A Design Pressure, DP (MPa) Design Temperature, TS ( -40 ~ 130 Maximum Allowable pressure (MPa) Weight (kg) Marking Connection Volume Initial Oil Charge Type Part No. Category Litres Litres RSPW 55855 5/8‘‘...