CAUTION
Electric Shock Hazard.
Can cause personal injury or equipment damage.
Do not attempt to remote-mount the power supply
without the remote mount kit. The special high voltage
wire in the kit has extra thick insulation to protect
against electric shock from the high voltage carried
between the air cleaner cells and the power supply.
Standard NEC class 1 wire is rated for only 600 volts
and will fail if used. Do not try to pull any other wires
through the flexible conduit in the kit.
Mount Remote Base
Select an easily accessible location for the power supply
within reach of the conduit assembly. Make sure the on-off
switch and neon light are readily visible.
Mount the remote mounting base using four screws
(obtained locally).
Mount Power Box and Junction Box
Loosen the screws holding the power supply; lift it slightly to
clear the screws, then pull it straight away from the junction
box to remove. Remove and retain screws. Set aside.
Remove the cover from the junction box. Set aside.
Disconnect the two leadwires from the quick connect
terminals in the junction box. See Fig. 15.
Remove the junction box from the cabinet.
Remove the knockout on the side of the junction box and
connect the end of the conduit assembly with the shorter
leadwires. See Fig. 16.
Install ground terminal in junction box. See Fig. 16.
Connect the leadwires as shown in Fig. 16.
Fasten the junction box to the base with the two screws
removed earlier.
Replace the junction box cover and secure with screw
removed earlier.
Loosely reinsert screws into power supply base. Plug the
power supply into the junction box. Push it straight in to
avoid bending the plug. Tighten screws. See Fig. 17.
AIR CLEANER
JUNCTION BOX
CONDUIT
CONNECTOR
1
SCREW AND QUICK-CONNECT TERMINAL IN 136377A REMOTE MOUNT KIT.
1
QUICK-
CONNECT
TERMINAL
Fig. 16. Make wiring connections in junction box.
9
F50E DUCT MOUNTED ELECTRONIC AIR CLEANER
Fig. 15. Disconnect the wires and remove the
power box and junction box.
TOP VIEW
RED
LEADWIRE
BLACK
LEADWIRE
SCREW
M4696
WHITE GROUND
LEADWIRE
M6499
68-0072—5