Technical specifications

Power Supply
Signal inputs
Signal outputs
Environment
Standards
General

Dimensions [mm] (inch)

Doc: 70-00-0588 V1.0, 20180928
Subject to alteration
Operating Voltage
Power Consumption
Electrical Connection
Temperature Input
Range
Accuracy
Analog Outputs
Output Signal
Resolution
Maximum Load
Operation
Climatic Conditions
Temperature
Humidity
Transport & Storage
Climatic Conditions
Temperature
Humidity
Mechanical Conditions
conform according to
EMC Standard
89/336/EEC
EMEI Standard 73/23/EEC
Product standards
Automatic electrical controls for
household and similar use
Special requirement on
temperature dependent controls
Degree of Protection
Safety Class
Housing material:
Dimensions (H x W x D)
Weight (including package)
60 (2.4)
© Vector Controls GmbH, Switzerland
24 V AC/DC ± 10 %, 50/60 Hz, Class 2 48VA max
Max. 1.5 VA
Terminal Connectors,
wire 0.34-2.5 mm
0-50 °C (32-122 °F)
0.5 K
AO1, AO2
DC 0-10 V
9.76 mV (10 bit)
10 mA
To IEC 721-3-3
class 3 K5
0-50 °C (32-122 °F)
<95 % r.H. non-condensing
To IEC 721-3-2 and IEC 721-3-1
class 3 K3 and class 1 K3
-25-70 °C (-13-158 °F)
<95 % r.H. non-condensing
class 2MT2
EN 61 000-6-1/ EN 61 000-6-3
EN 60 730 –1
EN 60 730 – 2 – 9
IP30 to EN 60529
III (IEC 60536)
Fire proof ABS plastic (UL94 class V-0)
Front part: 60 x 60 x 8 mm (2.4" x 2.4" x 0.3")
Power case: ø 58 x 27 mm (ø 2.3" x 1.1")
115 g (4.0 oz)
8 (.3)
27 (1.1)
www.vectorcontrols.com
TCT-MZ

Technical data

2
(AWG 24...12)
Page 2