Rev A (ACT-VCC-1000-DC) Summary This manual describes the ACT-VCC-1000 DC Air Conditioner and includes the product description, working principles, wiring diagrams, operating instructions, routine maintenance, troubleshooting, and technical specifications of this model. Table of Contents Summary ............................2 Instructions ................3 Product Overview ................
Be sure to read this manual carefully before installing or operating the unit. • To be covered by ACT’s warranty and access normal warranty service, the user(s) must comply with all local and industry standards, as well as with the instructions in this User Manual.
Rev A (ACT-VCC-1000-DC) 2.2 Application Notes This product is intended for use in industrial equipment applications that utilize a 48V DC power supply. The purpose of its installation is to control cabinet temperature between 20 to 45℃; keeping within this range will ensure that all thermal sensors operate as intended.
Rev A (ACT-VCC-1000-DC) 2.5 Technical Specifications Table 2.1 Technical Specifications Note: Parameters will be subject to the latest specification 2.6 Air Circulation and Remote Mounting Internal circulation and external circulation of the air is shown in Figure 2.3. Ducting and a separating plate are not required for enclosure mounting applications.
Rev A (ACT-VCC-1000-DC) 2.7 Operation of the Unit When the unit is turned on, it will perform a self-test before starting standard operation. If any faults are detected during the self-test, the system goes into the ‘fault’ mode; an alarm will be triggered and an error code will be shown on the LED display to alert the user.
*Heating functions are optional and not included on all units. The above parameters can be accessed through RS485 communication if necessary. For questions, please contact ACT’s sales staff at 717-295-6061. 2.10 Alarm and fault management During normal operation, the LED displays the return air temperature leaving the air conditioner. An alarm signal will alert the user to an error and the alarm code error message will be displayed alternately with the return air temperature.
Rev A (ACT-VCC-1000-DC) Low-temperature warning DC Power overvoltage warning DC Power undervoltage warning Refrigerant circuit pressure is too high warning Refrigerant circuit pressure is too low warning E13* Heater current overload warning E14* Heater current too low warning Return air temperature sensor fail warning...
Rev A (ACT-VCC-1000-DC) 4. Unpacking and Acceptance • Make sure the package is upright as shown in Figure 4.1 before you open the package, Figure 4.1 packaging • Please check that the packing straps are unbroken and that the wooden box is undamaged, not deformed or wet.
Rev A (ACT-VCC-1000-DC) Figure 5.2 Dimensions for cut-out in enclosure door Installation steps: 1. Mark the cabinet with the cut-out dimensions according to Figure 5.2 2. Cut out the shaded area 3. Remove the product from the shipping crate with care 4.
Page 11
Rev A (ACT-VCC-1000-DC) Table 5.1: Wiring Requirements MODEL ACT-VCC-1000-DC Power supply - 48 VDC* ( GND/RTN: positive, -48: negative) Power supply range -42 VDC ~ - 60 VDC. DC power supply source capacity ≥15Amps @ 48VDC Main power supply cable size ≥14AWG (UL 1015)...
Rev A (ACT-VCC-1000-DC) Figure 5.3 System wiring diagram Intfan Extfan RS485 -48V CTRL T/R- T/R+ 6. Running and Testing 6.1 Pre-operational checks After Air Conditioner is installed and the electrical connection is completed, please complete the following checklist: Table 6.1 Pre-operational checks...
Rev A (ACT-VCC-1000-DC) 6.2 Operating the Unit Apply power to the unit. The product will first run a self-test program, and then the unit will run normally. (Self-test: Refer to “Section 2.7: Operation”) • If there is any trouble during the self-test, the alarm will be triggered: the LED Display will flash with alarm error codes, Refer to “Table:2.3 Error Code meanings”...
Rev A (ACT-VCC-1000-DC) Setting Display Parameters: Press the "M" key for 5 seconds, causing the system to enter into parameter setting mode. The display will show the “Pxx” code. • Use arrow "" keys to choose the desired item. •...
Page 15
Rev A (ACT-VCC-1000-DC) 7.1.3 Routine Maintenance Table 7.3 Routine maintenance NUM. Check items Check methods Solution Turn off the supply power Tug on the power line with moderate force and check Power line If a power line is loose or loosening,...
Other system faults 7.2 Service and Repair Warranty period: 1-year limited warranty Warranty Section from ACT’s PURCHASE ORDER TERMS AND CONDITIONS • Buyer’s Property. All drawings, tools, fixtures, materials and other items supplied or paid for by Buyer shall be and remain the property of Buyer. All such items shall be used only in the performance of work under this Order unless Buyer consents otherwise in writing.
Page 17
Payment for any Goods shall not be deemed an acceptance hereof. Please see ACT’s current full Terms & Conditions: https://www.1-act.com/termsandconditions/ Disclaimer The warranty is limited to the delivered product(s) and ACT is not responsible for any loss that may be derived by equipment failure. Questions or Comments? ACT Quality Department: quality@1-act.com...