Electric Shock Hazard - Carrier WeatherExpert 50LC 07 Series Installation Instructions Manual

Single package rooftop cooling only with r-410a refrigerant
Table of Contents

Advertisement

6.
Caulk the ends of the joint between the unit top panel and
the hood top.
7.
Replace the filter access panel.
INDOOR
COIL
ACCESS
PANEL
Fig. 12 — Indoor Coil Access Panel Relocation
LEFT
HOOD
SIDE
19 1/16"
B
(483mm)
HOOD DIVIDER
Fig. 13 — Economizer Hood Construction
DIVIDER
CLEANABLE
ALUMINUM
FILTER
BAROMETRIC
RELIEF
Fig. 14 — Economizer Filter Installation
Step 9 — Install External Condensate Trap and
Line
The unit has one
/
-in. condensate drain connection on the end
3
4
of the condensate pan and an alternate connection on the bot-
tom. See Fig. 15. Unit airflow configuration does not
TOP
PANEL
TOP
PANEL
CAULK
HERE
INDOOR
COIL
ACCESS
PANEL
TOP
PANEL
INDOOR COIL
ACCESS PANEL
SCREW
33 3/8"
(848mm)
OUTSIDE
AIR
HOOD
FILTER
FILTER
CLIP
determine which drain connection to use. Either drain connec-
tion can be used with vertical or horizontal applications.
To use the alternate bottom drain connection, remove the red
drain plug from the bottom connection (use a
et drive extension) and install it in the side drain connection.
The piping for the condensate drain and external trap can be
completed after the unit is in place. See Fig. 16.
CONDENSATE PAN (SIDE VIEW)
STANDARD
SIDE DRAIN
Fig. 15 — Condensate Drain Pan (Side View)
MINIMUM PITCH
1" (25mm) PER
BASE RAIL
10' (3m) OF LINE
TO ROOF
DRAIN
NOTE: Trap should be deep enough to offset maximum unit static
difference. A 4-in. (102 mm) trap is recommended.
Fig. 16 — Condensate Drain Piping Details
All units must have an external trap for condensate drainage.
Install a trap at least 4-in. (102 mm) deep and protect against
freeze-up. If drain line is installed downstream from the exter-
nal trap, pitch the line away from the unit at 1-in. per 10 ft
(25 mm in 3 m) of run. Do not use a pipe size smaller than the
unit connection (
3
/
-in.).
4
Step 10 — Make Electrical Connections

ELECTRIC SHOCK HAZARD

Failure to follow this warning could result in personal injury or
death.
Unit cabinet must have an uninterrupted, unbroken electrical
ground to minimize the possibility of personal injury if an
electrical fault should occur. This ground may consist of elec-
trical wire connected to unit ground lug in control compart-
ment, or conduit approved for electrical ground when installed
in accordance with NEC; ANSI/NFPA 70, latest edition (in
Canada, Canadian Electrical Code CSA [Canadian Standards
Association] C22.1), and local electrical codes.
NOTE: Field-supplied wiring shall conform with the limitations
of minimum 63°F (33°C) rise.
12
1
/
-in. square sock-
2
ALTERNATE
DRAIN
PLUG
BOTTOM DRAIN
(FACTORY-INSTALLED)
3 in. (76 mm)
MIN
OPEN
VENT
DRAIN PLUG
WARNING
SEE NOTE
ROOF
CURB

Advertisement

Table of Contents
loading

Table of Contents