Technical Data; Firing Rate; Minimum Gas Pressure - 2Nd Stage Output - Riello GI/EMME 300 Installation, Use And Maintenance Instructions

Dual fuel gas-oil/gas burners
Table of Contents

Advertisement

Available languages

Available languages

TECHNICAL DATA

MODEL
Typ
Thermal power
Fuels
Minimum gas pressure (measured at the test point)
Maximum gas pressure
Electrical supply
Fan - capacitor motor
Pump - capacitor motor
Ignition transformer
Pump
Operation
The burner conforms to IP 40 level of insulation as per EN 60529.

FIRING RATE

Minimum output at 1st stage: 107 kW - 9 kg/h

MINIMUM GAS PRESSURE - 2nd STAGE OUTPUT

Pressure: measured at the test point with combustion chamber at 0 mbar
natural gas (G 20)
LPG (G 31)
GI / EMME 300
107 / 175 - 332 kW 92.000 / 150.000 - 286.000 kcal/h
Oil, max. viscosity at 20 °C: 6 mm
Natural gas with Pci 8.600 kcal/m
LPG with Pci 22.200 kcal/m
Maximum capacity requires:
- 9.3 mbar with natural gas;
- 11 mbar with LPG.
Combustion chamber at 0 mbar.
35 mbar
single-phase 230 V +/- 10% 50 Hz
1.85 A / 230 V - 8 µF
1.4 A / 230 V - 6.3 µF
primary 1.85 A / 230 V - secondary 1x 8 kV 30 mA
Output 50 kg/h at 12 bar - max. pressure 15 bar
Two stages
Gas pressure test point
15
495 T1
2
/s (1,5 °E)
3
3
D1936
kW
kcal/h
D1937
kW
kcal/h
GB
D1956

Advertisement