Default I/O connections
The default I/O connections of the Water default configuration are shown below.
Wire sizes: 0.14...2.5 mm
Tightening torques: 0.5...0.6 N·m (0.4 lbf·ft).
1...10 kohm
Max.
500 ohm
Total load capacity of the Auxiliary voltage output +24V (X2:10) is 6.0 W (250 mA / 24 V DC).
2
(26...16 AWG): All terminals.
X1
Reference voltage and analog inputs and outputs
1
SCR
2
AI1
3
AGND
4
+10V
5
AI2
6
AGND
7
AO1
8
AO2
9
AGND
X2 & X3 Aux. voltage output and programmable digital inputs
10
+24V
11
DGND
12
DCOM
13
DI1
14
DI2
15
DI3
16
DI4
17
DI5
18
DI6
Relay outputs
X6, X7, X8
19
RO1C
20
RO1A
21
RO1B
22
RO2C
23
RO2A
24
RO2B
25
RO3C
26
RO3A
27
RO3B
Embedded fieldbus
X5
29
B+
30
A-
31
DGND
S4
TERM
S5
BIAS
Safe torque off
X4
34
OUT1
35
OUT2
36
SGND
37
IN1
38
IN2
X10
24 V AC/DC
40
24 V AC/DC+ in Ext. 24V AC/DC input to power up the control unit
24 V AC/DC- in when the main supply is disconnected.
41
EN – Quick installation guide 7
Signal cable shield (screen)
Output frequency/speed reference
Analog input circuit common
Reference voltage 10 V DC
Actual feedback: 0...10 V
Analog input circuit common
Output frequency: 0...10 V
Output current: 0...20 mA
Analog output circuit common
Aux. voltage output +24 V DC, max. 250 mA
Aux. voltage output common
Digital input common for all
Stop (0) / Start (1)
Not configured
Constant frequency/speed selection
Not configured
Not configured
Not configured
Ready run
250 V AC / 30 V DC
2 A
Running
250 V AC / 30 V DC
2 A
Fault (-1)
250 V AC / 30 V DC
2 A
Embedded fieldbus, EFB (EIA-485)
Termination switch
Bias resistors switch
Safe torque off. Factory connection. Both
circuits must be closed for the drive to start. See
chapter
(3AXD50000
[English]).
: 0...10 V
EN
DA
DE
ES
FI
FR
IT
PL
PT
RU
in the
SV
TR
ZH