Page 2
Typical calibration frequencies for most applications are between 3 and 6 months, but can be required more often or less often based on your usage. 35-3010RKA-08 Sample-Draw Detector...
Page 3
Product Warranty RKI Instruments, Inc. warrants gas alarm equipment sold by us to be free from defects in materials, workmanship, and performance for a period of one year from date of shipment from RKI Instruments, Inc. Any parts found defective within that period will be repaired or replaced, at our option, free of charge.
WARNING: When using the 35-3010RKA-08, you must follow the instructions and warnings in this manual to assure proper and safe operation of the 35-3010RKA-08 and to minimize the risk of personal injury. Be sure to maintain and periodically calibrate the 35-3010RKA-08 as described in this manual.
The housing door is hinged on the left side and is secured by two latches on the right side. Four mounting feet are attached to the back of the housing (one at each corner). Use the 2 • 35-3010RKA-08 Sample-Draw Detector...
It prevents water and other liquids from contaminating the flow system. Replace the filter when it appears dirty, discolored, or clogged. If a liquid other than water is drawn into the filter, replace the filter as soon as possible. 35-3010RKA-08 Sample-Draw Detector • 3...
Page 8
This causes a downscale reading at the monitor on these channels. The low flow level is factory-set at 0.6 SCFH (±0.2 SCFH). NOTE: There is no low flow indication for the LEL or oxygen channels. 4 • 35-3010RKA-08 Sample-Draw Detector...
The CO sensor position in the flow block is occupied by a plastic dummy plug in the 35-3010RKA-08. Hydrogen Sulfide Gas Sensor The H S sensor position in the flow block is occupied by a plastic dummy plug in the 35-3010RKA-08. 35-3010RKA-08 Sample-Draw Detector • 5...
Page 10
The test points are located on the left side of the transmitter and are labeled TP+ and TP-. A 100 mV - 500 mV output is available at these test points for use during calibration. 6 • 35-3010RKA-08 Sample-Draw Detector...
Page 11
The test points are located on the top of the transmitter on either side of the transmitter interconnect terminal strip. They are labeled TP+ and TP-. A 100 mV - 500 mV output is available at these test points for use during calibration. 35-3010RKA-08 Sample-Draw Detector • 7...
Page 12
Interconnect Terminal Strip The interconnect terminal strip is the sixteen-point terminal strip near the bottom edge of the main circuit board. Use the interconnect terminal strip to connect the sample-draw detector to power and an external device. 8 • 35-3010RKA-08 Sample-Draw Detector...
Page 13
H S channels which will cause a downscale reading at the controller or recording device. The 35-3010RKA-08 does not have a CO or H S sensor installed so the relay has no effect in this version of the 35-3010RK.
NOTE: The sample-draw detector is shipped with the mounting feet “tucked under” the housing to protect the mounting feet during shipment. Slightly loosen the screw that secures one of the mounting feet to the housing, then rotate the mounting foot 180 degrees (see Figure 6). 10 • 35-3010RKA-08 Sample-Draw Detector...
Route the cable or wires in conduit leading from the sample-draw detector to the controller. Connect the drain wire to an available chassis ground at the controller end. RKI controllers typically have a ground stud that can be used to ground the cable’s drain wire. 35-3010RKA-08 Sample-Draw Detector • 11...
Page 16
4/20 F ee db ack LEL (C on trolle r 24 VD C (Controller Transmitter Tra nsm itter 24 VD C Te rm inals) 4-20 ( Fe edba ck) Te rm inals) Figure 7: External (Field) Wiring, Sample-Draw Detector 12 • 35-3010RKA-08 Sample-Draw Detector...
Page 17
CO an d H2 S S en so rs Plug I nto ( Not (Not Far S ide of P r eamp Use d) Use d) Circui t B oard Figure 8: Internal (Factory) Wiring, Sample-Draw Detector 35-3010RKA-08 Sample-Draw Detector • 13...
If necessary, use a small flat-blade screwdriver to adjust the LEL transmitter’s zero pot until the voltmeter reading is 100 mV (± 2 mV). Verify a voltmeter reading of 434 mV (± 2 mV) at the oxygen transmitter. 14 • 35-3010RKA-08 Sample-Draw Detector...
Verify a reading of 0 %LEL for the IR CH channel (100 mV at the LEL transmitter test points) and 20.9% for the oxygen channel (434 mV at the oxygen transmitter test points). Investigate significant changes in the reading. 35-3010RKA-08 Sample-Draw Detector • 15...
The troubleshooting guide describes symptoms, probable causes, and recommended action for problems you may encounter with the sample-draw gas detector. NOTE: This troubleshooting guide describes sample-draw detector problems only. See the instruction manual for the controller if it exhibits any problems. 16 • 35-3010RKA-08 Sample-Draw Detector...
Page 21
If the fail condition continues, replace the sensor from the problem channel or channels as described later in this section. If the fail condition continues, contact RKI Instruments, Inc. for further instruction. Slow or No Response/Difficult or Unable to Calibrate Symptoms •...
If the calibration/response difficulties continue, replace the sensor as described later in this section. If the calibration/response difficulties continue, contact RKI Instruments, Inc. for further instruction. Replacing Components of the Sample-Draw Detector This section includes procedures to replace the sensors, the hydrophobic filter, and the charcoal filter.
Replacing the Charcoal Filter NOTE: The charcoal filter does not normally need to be replaced in the 35-3010RKA-08 because it does not include a CO sensor. Turn off or unplug power to the controller. Locate the charcoal filter. It is located along the upper edge of the detector housing.
Disconnect the sample tubing from the inlet line. Unscrew the regulator from the zero air calibration cylinder. Leave the sample tubing connected to the regulator. Setting the Response Reading Screw the regulator into the methane calibration cylinder. 20 • 35-3010RKA-08 Sample-Draw Detector...
Setting the Zero Reading Screw the regulator into the 100% nitrogen calibration cylinder. Connect the calibration kit sample tubing to the regulator. Connect the sample tubing from the regulator to the inlet line at or near the sample- 35-3010RKA-08 Sample-Draw Detector • 21...
Wait 1 to 2 minutes to allow the calibration gas to be drawn out and the reading to stabilize. Close the housing door. Store the components of the calibration kit in a safe and convenient place. 22 • 35-3010RKA-08 Sample-Draw Detector...
Need help?
Do you have a question about the 35-3010RKA-08 and is the answer not in the manual?
Questions and answers