Mitsubishi Electric Mr.Slim PUHZ-P100VKA Service Manual page 69

Hide thumbs Also See for Mr.Slim PUHZ-P100VKA:
Table of Contents

Advertisement

Indication
Outdoor controller board
LED1 (Green) LED2 (Red)
Abnormality of comp. surface
3 blinking 1 blinking
thermistor(TH33) and discharge
temperature (TH4)
Abnormality of superheat due
to low discharge temperature
2 blinking
Abnormal high pressure (High
pressure switch 63H operated.)
3 blinking
Abnormality of outdoor fan
motor rotational speed
Compressor overcurrent
4 blinking
breaking(Startup locked)
Compressor overcurrent breaking
Abnormality of current sensor (P.B.)
Abnormality of power module
Open/short of discharge thermistor (TH4)
5 blinking
and comp. surface thermistor (TH33)
Open/short of outdoor thermistors
(TH6, TH7 and TH8)
6 blinking
Abnormality of heatsink
temperature
7 blinking
Abnormality of voltage
4 blinking
1 blinking
Abnormality of room temperature thermistor (TH1)
Abnormality of pipe temperature thermistor /Liquid (TH2)
Abnormality of pipe temperature
thermistor/Condenser-Evaporator
2 blinking
Abnormality of drain sensor (DS)
Float switch(FS) connector open
Indoor drain overflow protection
3 blinking
Freezing (cooling)
Abnormality of pipe
4 blinking
temperature
*Check code displayed on remote controller
**Refer to indoor unit's Service Manual.
OCH670
Check
Contents
code*
1Check if stop valves are open.
U2
2Check if connectors (TH4, TH33, LEV-A and LEV-B) on outdoor controller
board are not disconnected.
3Check if unit is filled with specified amount of refrigerant.
U7
4Measure resistance values among terminals on indoor valve and
outdoor linear expansion valve using a tester.
1Check if indoor/outdoor units have a short cycle on their air ducts.
U1
2Check if connector (63H) on outdoor controller board is not disconnected.
3Check if heat exchanger and filter is not dirty.
4Measure resistance values among terminals on linear expansion valve
using a tester.
U8
1Check the outdoor fan motor.
2Check if connector (TH3) on outdoor controller board is disconnected.
1Check if stop valves are open.
UF
2Check looseness, disconnection, and converse connection of
compressor wiring.
3Measure resistance values among terminals on compressor using a tester.
UP
4Check if outdoor unit has a short cycle on its air duct.
UH
U6
U3
1Check if connectors(TH3,TH4,TH6 ,TH7, TH8 and TH33) on outdoor
controller board and connector (CN6) on outdoor power board are
disconnected.
2Measure resistance value of outdoor thermistors.
U4
1Check if indoor/outdoor units have a short cycle on their air ducts.
U5
2Measure resistance value of outdoor thermistor(TH8).
U9
1Check looseness, disconnection, and converse connection of
compressor wiring.
2Measure resistance value among terminals on compressor using a tester.
3Check if power supply voltage decreases.
4Check the wiring of CN52C.
P1
1Check if connectors (CN20, CN21, CN29 and CN44) on indoor
controller board are not disconnected.
P2
2Measure resistance value of indoor thermistors.
P9
P4
1Check if connector (CN31)(CN4F) on indoor controller board is not
disconnected.
2Measure resistance value of indoor thermistors.
3Measure resistance value among terminals on drain pump using
P5
a tester.
4Check if drain pump works.
5Check drain function.
P6
1Check if indoor unit has a short cycle on its air duct.
2Check if heat exchanger and filter is not dirty.
3Measure resistance value on indoor and outdoor fan motors.
4Check if the inside of refrigerant piping is not clogged.
1Check if indoor thermistors(TH2 and TH5) are not disconnected from holder.
P8
2Check if stop valve is open.
3Check converse connection of extension pipe. (on plural units connection)
4Check if indoor/outdoor connecting wire is connected correctly.
(on plural units connection)
Error
Inspection method
69
Detailed
reference
page
P.35
P.36
P.35
P.36
P.38
P.39
P.38
P.36
P.35
P.36
P.36
P.37
to
38
**