Configuration of connection pipe

1. Standard length of connection pipe
• 16 ft.
2. Min. length of connection pipe is 9.8 ft.
3. Max. length of connection pipe and max. hight difference.
Cooling
Max length
capacity
of connec-
tion pipe
5000Btu/h
49 ft
(1465W)
7000Btu/h
49 ft
(2051W)
9000Btu/h
49 ft
(2637W)
12000Btu/h
65 ft
(3516W)
18000Btu/h
82 ft
(5274W)
4. The additional refrigerant oil and refrigerant charging required after
prolonging connection pipe
• After the length of connection pipe is prolonged for 32 ft at the basis of
standard length, you should add 0.17 oz of refrigerant oil for each additional
16 ft of connection pipe.
• The calculation method of additional refrigerant charging amount (on the
basis of liquid pipe):
Additional refrigerant charging amount = prolonged length of liquid pipe ×
additional refrigerant charging amount per meter.
• Basing on the length of standard pipe, add refrigerant according to the
requirement as shown in the table. The additional refrigerant charging
amount per meter is different according to the diameter of liquid pipe. See
the following sheet
Max
Cooling
height
capacity
difference
16 ft
24000Btu/h
(7032W)
16 ft
28000Btu/h
(820W)
16 ft
36000Btu/h
(10548W)
32 ft
24000Btu/h
(3516W)
32 ft
48000Btu/h
(14064W)
Max length
Max height
of connection
difference
pipe
82 ft
32 ft
98 ft
32 ft
98 ft
65 ft
98 ft
65 ft
98 ft
65 ft