Troubleshooting

Checking for Increased Wear of Fireclay

Increased fireclay wear can be observed in the substructure or in the curved bricking.
Fireclay must only be replaced when:
the curved bricking is broken downwards (not already in the event of formation of cracks or spalling)

fireproof panel located on the back of the fireclay can be seen in the substructure

Checking for increased
wear of fireclay
Check the recirculation system
Check damper
Check fireclay for discoloration
22
Vitoflex 300-RF Service & Maintenance

Cleaning in the area of the arch in the chimney
and in the area of the opening of the shut-off
valve

Recirculation must be hot at partial load

Damper must be installed

Damper must not be fully open (chimney draft
may be too strong)

If discoloration is visible in the fireclay

If there is discoloration, often halogen
substances have been burned