Set Clock; Heat Pump Configuration; Configure Advanced Setup - Bryant TEMPSURE COMMERCIAL THERMOSTAT P/N TSTATBBP220-LA Installation And Service Instructions Manual

Commercial thermostat
Table of Contents

Advertisement

THERMOSTAT
B
O
W2 Y2 R W1 Y1 G C
Fig. 3 — Typical Wiring (Single-Stage Cooling Units)
THERMOSTAT
B
O
W2 Y2 R W1 Y1 G C
2nd STAGE COMPRESSOR RELAY
Fig. 4 — Typical Wiring (Two-Stage Cooling Units)
Table 1 — Thermostat Wiring Terminations
EXISTING
WIRE
FUNCTION
DESIGNATION
G or F
Y1, Y, or C
W1, W, or H
Rh, R, M, Vr, or A
Power (24 v)
C
O/B
Reversing Valve
Y2
Second Stage Cooling
W2
Second Stage Heating
*Terminals C, W2, and Y2 may not be used in all applications.
†Used on Heat Pump applications only.
III. SET CLOCK
The Set Clock button allows the user to change the time and
day displayed on the thermostat. Press the Set Clock button.
The current time will blink on and off. Press the UP ARROW
and DOWN ARROW buttons until the correct time is shown.
Hold down the buttons to quickly move through the time dis-
play. The AM and PM annunciators will automatically change.
Hold down the Fan button while pressing UP ARROW or
DOWN ARROW to change the time by hours instead of min-
utes. To ensure the schedules are properly followed, make sure
that AM or PM is correct for the time chosen. When the cor-
rect time is shown, press the Mode button to modify the day
TYPICAL
UNIT
24 VAC COMMON
FAN RELAY
COMPRESSOR RELAY
1st STAGE HEAT CIRCUIT
24 VAC RETURN
2nd STAGE HEAT CIRCUIT
TYPICAL
UNIT
24 VAC COMMON
FAN RELAY
COMPRESSOR RELAY
1st STAGE HEAT CIRCUIT
24 VAC RETURN
2nd STAGE HEAT CIRCUIT
TERMINAL
CONNECTION
Fan
G
Cooling
Y1
Heating
W1/O/B
R
Common
C*
W1/O/B†
Y2*
W2*
of the week. The current day will blink on and off. Press the
UP ARROW and DOWN ARROW buttons until the correct
day is shown. Press the Set Clock button again to exit the
Set Time mode.
L
E
IV. HEAT PUMP CONFIGURATION
C
To configure the thermostat for heat pump operation, Ad-
G
vanced Setup Steps 3 (Heat Pump Operation) and 4 (Revers-
Y1
ing Valve Polarity) must be configured correctly. See the
O
Configure Advanced Setup section for information on config-
uring these options.
W1
NOTE: Some large commercial rooftop heat pump units (542J)
R
must be configured with Advanced Setup Step 3 (Heat Pump
Y2
Operation) set to OFF. Refer to the base unit instructions for
W2
more information.
V. CONFIGURE ADVANCED SETUP
To enter into the advanced setup screens of the thermostat,
press the Mode and Program buttons at the same time. The
Advanced Setup Step number is shown in the top right
corner of the thermostat screen. Use the Mode button to
advance through the steps. There are 15 Advanced Setup Steps.
See Table 2. Press the Program button at any time to exit the
L
Advanced Setup mode.
E
NOTE: Advanced Setup Steps 1 and 2 are configured with
C
the Set Clock button, and are not accessed through the
G
advanced setup screens.
Y1
O
A. Heat Pump Configuration (Steps 3 and 4)
W1
To set the thermostat for heat pump operation, Advanced Setup
R
Step 3 must be configured to ON. Use the UP and DOWN
ARROW buttons to configure the step. The default is OFF.
Y2
Press the Mode button to continue to Step 4. Step 4 is used to
W2
set the reversing valve polarity for the heat pump. The vari-
able can be set to either ''B'' or ''O.'' Set the reversing valve
polarity to the correct value depending on the application. The
default is ''O.''
NOTE: Step 4 will appear only if Step 3 is set to ON. Step 5
will appear only if Step 3 is set to OFF.
Table 2 — Advanced Setup Configuration
STEP
DESCRIPTION
1*
Time of Day
2*
Day of the Week
3
Heat Pump
Reversing Valve
4
Polarity
5
Electric Heat
6
Deadband
Forced Minimum
7
Temperature Difference
8
Cycles per Hour
9
Thermoglow™ Backlight
Reset Service
10
Filter Icon
Service Filter
11
Run Time
12
Temperature Units
13
Security Level
Maximum Allowable
14
Heat Set Point
Minimum Allowable
15
Cooling Set Point
*Accessed and configured through the Set Clock button.
—3—
RANGE
DEFAULT
12:00 AM -
12:00 AM
11:59 PM
Sunday through
Monday
Saturday
Off/On
Off
O/B
O
Off/On
Off
1 - 6 degrees
2
0 - 6 degrees
2
d, d1, 2 - 6
6
Off/On
On
0-1950 hrs
500 hrs
F/C
F
0 - 3
0
35 - 99 F (1-37 C)
80 F (27 C)
35 - 99 F (1-37 C)
65 F (18 C)