Download Print this page

Bryant ASPAS1BBA007 Specification Sheet page 3

Home standby - 7kw - 12kw - 15kw air-cooled gas engine generator sets
Hide thumbs Also See for BRYANT ASPAS1BBA007:

Advertisement

Home Standby - 7kW - 12kW - 15kW
TRANSFER SWITCH &
EMERGENCY LOAD CENTER
No. of Poles
Current Rating (amps) ......................................................100 ..........................................100 ......................................... 100
Voltage Rating (VAC) ....................................................... 250 ......................................... 250 ......................................... 250
Utility Voltage Monitor (fixed)
-Pick-up ........................................................................... 70% ........................................ 70% ....................................... 70%
-Dropout ......................................................................... 60% ....................................... 60% ....................................... 60%
Return to Utility ....................................................... approx. 13 sec .......................approx. 13 sec. ....................... approx. 13 sec.
Exerciser weekly for 12 minutes .................................. Standard .................................Standard .................................Standard
UL Listed ...................................................................... Standard .................................Standard .................................Standard
Dimensions (H" x W" x D") .......................................26.5 x 12.5 x 7 ...................... 26.5 x 12.5 x 7 ....................... 26.5 x 12.5 x 7
Total of Pre-wired Circuits .................................................. 8 ............................................ 10 ...........................................12
No. 15A 120V .......................................................... 5 ............................................ 3 ........................................... 5
No. 20A 120V .......................................................... 1 ............................................ 3 ........................................... 3
No. 15A 240V .......................................................... - ............................................ - ........................................... -
No. 20A 240V .......................................................... - ............................................ 1 ........................................... 1
No. 30A 240V .......................................................... 1 ............................................ 1 ........................................... 1
Circuit Breaker Protected
Available RMS Symmetrical
Fault Current @ 250 Volts ...................................10,000 .....................................10,000 ......................................10,000
W2
W1
H1
BRYANT, INC. • 7310 WEST MORRIS STREET • INDIANAPOLIS, IN 46231 • www.bryant.com
Printed in USA 10.05
Model ASPAS1BBA007
(7kW)
2
Mechanical Dimensions (in inches)
Current
No. of
Rating
Poles
100 UL Listed
2
H2
CATALOG NO. SS-ASPAS07-02
Model ASPAS1BBA012
Model ASPAS1BBA015
(12kW)
2
Height
Width
H1
H2
W1
W2
26.5
29.25
8.14
12.5
Terminal Wire Ranges
ATS Rated Amps
100A 2-Pole UL
Transfer Switch Features
(15kW)
• Electrically operated,
2
mechanically-held contacts for
fast, positive connections.
• Rated for all classes of load,
100% equipment rated, both
inductive and resistive.
• 2 pole, 250 VAC contactors.
• 160 millisecond transfer time.
• Dual coil design.
• Main contacts are silver plated or
silver alloy to resist welding and
sticking.
• NEMA 1 enclosure is standard on
the 100 amp switch.
Depth
7
Switch Terminal
Neutral Lug/Stud
1 x 1/0-12
1 x 3/8-16 Stud
All specifications are subject to change without notice.
Ground Lug
1 x 2/0-14

Advertisement

loading

This manual is also suitable for:

Bryant aspas1bba015Aspas1bba012 aspas1bba015