Installation and Owner’s Manual Air-cooled Automatic Standby Generators Model: ASPAX1BBA015 (13 kW NG, 15 kW LP) LISTED GENERAC POWER SYSTEMS, INC. *This manual should remain with the unit.* Not intended for use as Primary Power in place of utility or in life-support applications.
This manual contains pertinent owner’s information, including warranty, electrical diagrams, exploded views and lists of repair parts, for model: • Model ASPAX1BBA015 – 13 kW NG, 15 kW LP , V- twin GT-990 Engine OPERATION AND MAINTENANCE It is the operator's responsibility to perform all safety...
Introduction ...Inside Front Cover Read This Manual Thoroughly ... IFC Contents ... IFC Operation and Maintenance ... IFC How to Obtain Service ... IFC Safety Rules ...2 Standards Index ... 3 Section 1 – General Information ...4 Unpacking/Inspection ... 4 Location ...
IMPORTANT SAFETY INSTRUCTIONS 15 kW Generator SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe operation be copied and posted in potential hazard areas. Safety should be stressed to all operators, potential operators, service and repair technicians for this equipment. ...
be done around an operating unit, stand on an insulated, dry surface to reduce shock hazard. • Do not handle any kind of electrical device while standing in water, while barefoot, or while hands or feet are wet. DANGEROUS ELECTRICAL SHOCK MAY RESULT.
Section 1 — General Information 15 kW Generator DANGER Only qualified electricians or contractors should attempt such installations, which must comply strictly with applicable codes, standards and regulations. UNPACKING/INSPECTION After unpacking, carefully inspect the contents for damage. • This standby generator set has been factory sup- plied with a weather protective enclosure that is intended for outdoor installation only.
RECONFIGURING THE FUEL SYSTEM 1.9.1 15KW, 990CC ENGINES To reconfigure the fuel system from NG to LP , follow these steps: NOTE: The primary regulator for the propane supply is NOT INCLUDED with the generator. A fuel pres- sure of 11 to 14 inches of water column (0.4 to 0.5 psi) to the fuel inlet of the generator MUST BE SUPPLIED.
Section 1 — General Information 15 kW Generator 1.10.2 TRANSFER SWITCH 1.10.2.1 15 kW Units Transfer switches for use with this generator are sold separately and can be purchased from dealers. • Install any transfer switch in accordance with the instructions supplied with the transfer switch.
The following procedures are to be observed: • Wear full eye protection and protective clothing; • Where electrolyte contacts the skin, wash it off immediately with water; • Where electrolyte contacts the eyes, immediately flush thoroughly with water and seek medical attention;...
Section 2 — Post Installation Start-up and Adjustments 15 kW Generator DANGER Proceed with caution! Generator power voltage is now supplied to the transfer switch. Contact with live transfer switch parts will result in dan- gerous and possibly fatal electrical shock. 11.
With the generator running and loads powered by generator AC output, turn ON the utility power supply to the transfer switch. The following should occur: • After about six seconds, the switch should transfer loads back to the utility power source. •...
Section 3 — Operation 15 kW Generator ENGINE GOVERNOR ADJUSTMENT If both AC frequency and voltage are correspondingly high or low, adjust the engine governor as follows: 2.7.1 15 KW UNITS 1. Loosen governor clamp bolt (See Figure 2.3). Figure 2.3 — V-twin Engine Governor Adjustment Idle Spring Governor...
9. Allow the unit to cool. 10. Set the generator’s main circuit breaker to its OFF (or OPEN) position. 11. Set the generator's AUTO/OFF/MANUAL switch to OFF . Remove the 7.5A and 15A fuses from the generator control panel. Disconnect the battery cables as outlined in “General Hazards”...
Section 3 — Operation 15 kW Generator 3.3.2 120 VAC GFCI OUTLET The generator is equipped with an external 15 amp, 120 volt, GFCI convenience outlet that is located in the right rear of the generator enclosure. When the generator is running, in the absence of utility power, this outlet may be used to power items outside a home such as lights or power tools.
5. To crank and start the engine, set the AUTO/OFF/ MANUAL switch to MANUAL. 6. Let the engine stabilize and warm up for a few minutes. 7. Set the generator’s main circuit breaker to its ON (or CLOSED) position. The standby power source now powers the loads.
Section 4 — Maintenance 15 kW Generator 3.7.3 OVERCRANK This feature prevents the generator from damaging itself when it continually attempts to start and anoth- er problem, such as no fuel supply, prevents it from starting. The unit will crank and rest for a preset time limit.
Any attempt to crank or start the engine before it has been properly serviced with the recom- mended oil may result in an engine failure. 4.3.2 OIL CHANGE PROCEDURE To change the oil, proceed as follows: 1. Run the engine until it is thoroughly warmed up then shut OFF the engine.
Section 4 — Maintenance 15 kW Generator Figure 4.5 – Setting the Spark Plug Gap SET PLUG GAP AT 0.050 mm/0.020 inch BATTERY MAINTENANCE The battery should be inspected per the “Service Schedule”. The following procedure should be fol- lowed for inspection: 1.
• Make sure the piston is at Top Dead Center (TDC) of its compression stroke (both valves closed). To get the piston at TDC, remove the intake screen at the front of the engine to gain access to the flywheel nut.
Section 4 — Maintenance 15 kW Generator 4.12 OUT OF SERVICE PROCEDURE 4.12.1 REMOVAL FROM SERVICE If the generator cannot be exercised every seven days, and will be out of service longer than 90 days, pre- pare the generator for storage as follows: 1.
4.13 SERVICE SCHEDULE ATTENTION: It is recommended that all service work SYSTEM/COMPONENT X = Action R = Replace as Necessary * = Notify Dealer if Repair is Needed. FUEL Fuel lines and connections* LUBRICATION Oil level Oil filter COOLING Enclosure louvers BATTERY Remove corrosion, ensure dryness...
Section 5 — Troubleshooting 15 kW Generator TROUBLESHOOTING GUIDE Problem The engine will not crank. The engine cranks but will not start. The engine starts hard and runs rough. The AUTO/OFF/MANUAL switch 1. Defective switch is set to OFF , but the engine continues to run.
Section 8 — Exploded Views and Parts Lists 15 kW Generator Enclosure – Drawing No. 0F0080-C PRE PACKAGED UNITS ONLY...
Page 31
ITEM PART NO. QTY. DESCRIPTION 0C6140 ASSEMBLY, ENCLOSURE BASE 0D1901 ASSEMBLY, ENCLOSURE BASE (7KW) 0C6735 SUPPORT, ROOF FOLDING 0F0063 ENCLOSURE, FRONT 0C7062 ENCLOSURE, EXHAUST SIDE 0C7062A ENCLOSURE, EXHAUST SIDE (7KW) 0E8811 ENCLOSURE, SIDE & BACK 0E8811A ENCLOSURE, SIDE & BACK (7KW) 0E9873 ENCLOSURE, ROOF 0C7065...
Page 32
Section 8 — Exploded Views and Parts Lists 15 kW Generator Control Panel – Drawing No. 0E9162-J...
Page 33
ITEM PART NO. QTY. DESCRIPTION 0E7886A CIRCUIT BREAKER 30A X 2P 240V (7KW) 0E7886E CIRCUIT BREAKER 50A X 2P 240V (12KW) 0E7886J CIRCUIT BREAKER 65A X 2P 240V (13/15KW) 0A1801 ASSEMBLY, BATTERY CHARGER ENGINE 083049 ASSEMBLY, POTTED REGULATOR 0C2174 RELAY, 12V 25A SPST 075210A BLOCK 1 POSITION 0D3062...
Page 34
Section 8 — Exploded Views and Parts Lists 15 kW Generator GT-990 Engine – Drawing No. 0F4715-B Part 1...
Section 9 – Warranty 15 kW Generator NOTE: This Emission Control Warranty Statement pertains to this product only IF the generator size is 15 kW or below. CALIFORNIA AND FEDERAL EMISSION CONTROL WARRANTY STATEMENT The California Air Resources Board (CARB) and the United States Environmental Protection Agency (EPA), together with Generac Power Systems, Inc.
Emission Control System Warranty (ECS Warranty) for 1997 and later model year engines: (a) Applicability: This warranty shall apply to 1997 and later model year engines. The ECS Warranty Period shall begin on the date the new engine or equipment is purchased by/delivered to its original, end-use purchaser/owner and shall continue for 24 consecutive months thereafter.
Page 44
For a period of two years from the date of original sale, warrants that its generator will be free from defects in material and workman- ship for the items and period set forth below. Bryant will, at its option, repair or replace any part which, upon examination, inspection and testing by a Bryant Dealer, is found to be defective.