PERTRONIC INDUSTRIES LTD
INSTALLATION NOTE
PS2 SOUNDER
Overview
The PS2 Sounder is one of a range of sounders manufactured by Pertronic Industries. The PS2
generates the evacuation and alert tones as specified by AS2220. The PS2 can also be used to
generate an alert signal acceptable to NZS4512:1997 (Amendment Two) by giving an
evacuation tone sweep every 15 seconds.
The PS2 has a maximum sound pressure level of 98dBA with a sound distribution pattern shown
below. The sound level may be adjusted by the volume control.
The PS2 is normally connected to the monitored bell or sounder circuit of a fire alarm panel and
to the LED drive output of a conventional or analogue addressable detector. The PS2 will sound
the evacuation tone when the detector is in alarm. If the bell circuit is reversed when the detector
is normal, the evacuation tone or alert tone will be sounded—depending on the state of the
terminal or jumper J3 of the PS2.
ALERT IN
The PS2 may also be powered from the analogue addressable loop. In this case, the PS2 will
sound the evacuation tone when the detector is in alarm.
The PS2 may be mounted in a standard single-gang electrical flush-box fitting and is supplied
with a protective plastic cover for installation and building construction use.
Specification
Dimensions:
Colour Options:
Sound Level Output:
Power Requirements:
Controls:
DETECTOR IN
J4 for conventional or analogue addressable detectors:
ALERT IN
Volume Control
Multiple Operation:
NOTE:
Pertronic Industries Ltd
117mm (height)x 74mm (width), 12mm (depth above flush-box)
Designed to fit into a standard flush-box fitting.
Red or White.
Sound pressure level at 1m ( 3dB) Alert, Evacuation: 95dBA (12V)
terminal (Supplied from the bell circuit or analogue loop):
BELL IN
Operating Voltage
Quiescent current (non alarm)
Operating current (alarm state) 8mA average, 12mA peak
,
DETECTOR OUT
Connect the detector LED output to the corresponding +/- terminals.
Insert link for conventional detectors.
Remove link for analogue addressable detector.
,
for externally operated AS2220 tone control:
ALERT OUT
Open circuit for Evacuation on Bell reversal,
0V for Alert on Bell reversal.
J3 for internally operated AS2220 tone control:
Insert link for Alert on Bell reversal.
Remove link for Evacuation on Bell reversal.
pcb-mounted potentiometer to adjust sound output
level. 20dB range.
Up to 5 PS2 sounders may be controlled by the LED output of one
detector.
J4 must be REMOVED for ANALOGUE detectors
J4 must be FITTED for CONVENTIONAL detectors
1 of 4
9.5V to 30Vdc
1.2A (12V, 24V)
14mA average, 22mA peak
for detector activation (Evacuation).
0301-PS2 Sounder Issue7 Oct 2002
98dBA (24V)
(12V)
(24V).

Advertisement

loading

Summary of Contents for Pertronic PS2

  • Page 1 The sound level may be adjusted by the volume control. The PS2 is normally connected to the monitored bell or sounder circuit of a fire alarm panel and to the LED drive output of a conventional or analogue addressable detector. The PS2 will sound the evacuation tone when the detector is in alarm.
  • Page 2 Refer to figure 5 for the location of J3. Up to 5 detectors may be connected in parallel to the Detector IN terminal to activate the PS2 from different detectors. Similarly, one detector can be wired to up to 5 PS2 sounders to activate multiple sounders from one detector.
  • Page 3 System Sensor B501 Detector 2(+) 2(+) 2(+) 1(-) 1(-) 1(-) Base or Pertronic PSB One detector may Multiple detectors may operate up to 5 sounders operate up to 5 sounders Pertronic Industries Ltd 3 of 4 0301-PS2 Sounder Issue7 Oct 2002...
  • Page 4 ANALOGUE detectors * J3 inserted for alert mode J4 must be FITTED for CONVENTIONAL detectors J4 fitted with an analogue detector may cause a bell fault. Fig 6 AS2220 tone characteristics Pertronic Industries Ltd 4 of 4 0301-PS2 Sounder Issue7 Oct 2002...