Download Print this page
Pertronic PSBAS2220 Datasheet

Pertronic PSBAS2220 Datasheet

Sounder base

Advertisement

Quick Links

PERTRONIC INDUSTRIES LTD
DATASHEET
Pertronic Sounder Base (PSBAS2220)
Overview
The Pertronic Sounder Base (PSBAS2220) is an
analogue addressable plug-in detector base with built-in
sounder. The PSBAS2220 generates a tone when the
detector is in alarm, or when directly activated by a bell
circuit.
The PSBAS2220 communicates with any Pertronic
analogue addressable fire alarm control panel via the AA
loop. The base connections connect the sounder base to
the analogue addressable loop, and internally to the LED
drive output of the analogue addressable detector.
When the detector is in the alarm state, the sounder base
generates NZS 4512:2010 Appendix F evacuation or alert
signals, depending on the position of switch S1. (Switch
S1 is accessible only when the unit is removed from its
mounting base.)
The unit may also be powered from a supervised bell
or sounder circuit via the SNDR IN terminals. If the
bell circuit is activated, the evacuation signal will be
generated, irrespective of the detector status.
Features
» Configurable NZS 4512:2010 Appendix F sound
patterns when detector active:
» Switch S1 DOWN: Evacuation signal
» Switch S1 UP: Alert signal
» Sounds evacuation signal when SNDR IN activated
Specification
Sound Pressure
Level at 1 m (± 3 dB)
Analogue
Addressable Loop
connection only
Bell Driver
connected
with Analogue
Addressable Loop
Height
Mounting Flange Diameter
Colour
Note: Operating current sourced from the power supply with the greater voltage (usually bell driver).
Alert
Evacuation
Operating Voltage
Quiescent Current (non-alarm)
Operating Current (alarm state)
(see note)
Quiescent Current (non-alarm)
Operating Current (alarm state)
Below Ceiling (when recessed)
Above Ceiling (when recessed)
With Surface Mounted Extension Cover
Surface Mounted Extension Cover
Pertronic Analogue Addressable
Sounder Base (PSBAS2220)
The PSBAS2220 is normally mounted by recessing it
into the ceiling. A mounting ring is available for surface
mounted applications.
» Configurable to generate an alert signal acceptable
to NZS4512:1997 by giving an evacuation tone
sweep every 15.5 seconds
» 95 dBA maximum sound pressure level
87 dBA
95 dBA
15 to 30 V dc
0.4 mA (24 V)
8 mA average, 12 mA peak, 15 V
14 mA average, 22 mA peak, 24 V
0.2 mA @ 24 V (Analogue addressable loop)
0.2 µA @ 24 V (Bell driver)
8 mA average, 12 mA peak, 15 V
14 mA average, 22 mA peak, 24 V
31 mm (including B501 base)
35 mm
66 mm
35 mm
122 mm
Ivory

Advertisement

loading

Summary of Contents for Pertronic PSBAS2220

  • Page 1 Overview The Pertronic Sounder Base (PSBAS2220) is an analogue addressable plug-in detector base with built-in sounder. The PSBAS2220 generates a tone when the detector is in alarm, or when directly activated by a bell circuit. The PSBAS2220 communicates with any Pertronic analogue addressable fire alarm control panel via the AA loop.
  • Page 2 Unless explicitly stated otherwise, this document provides typical specifications and nominal dimensions. Actual product performance and dimen- sions may vary. All information in this document is subject to change. Please consult Pertronic Industries or visit our web site for up to date information. PERTRONIC® is a registered trademark of Pertronic Industries Limited.