PERTRONIC INDUSTRIES LTD
PS1-T3 Sounder - Installation Instructions
Overview:
The PS1-T3 generates 'Evacuation' tones compliant to AS2220 or ISO8201
The PS1-T3 Sounder has a maximum sound pressure level of 98dBA with a sound
distribution pattern shown below. The sound level may be adjusted by a Volume control.
The PS1-T3 Sounder is normally connected to the monitored Bell or Sounder circuit of a
Fire Alarm Panel and is activated when the Sounder circuit voltage polarity is reversed in
the 'Alarm' state.
The PS1-T3 Sounder may be mounted in a standard single-gang electrical flush-box
fitting and is supplied with a protective plastic cover for installation and building
construction use.
Specification:
Dimensions:
Colour Options:
Sound Level Output:
Power Requirements:
Quiescent current (Non-Alarm state)
Operating current (Alarm state – T3 tone)
(Alarm state – AS2220 tone)
Controls:
Volume Control:
Tone Characteristics:
Sound Pressure Distribution:
WALL
Horizontal
Plane
-45deg
PS1-T3 Sound Distribution at 1 metre
Pertronic Industries Pty Ltd
117 x 74 x 12
- designed to fit into a standard electrical flush-box fitting.
Red or White.
Sound pressure level at 1m (peak ± 3dB)
Evacuation, Alert:
BELL IN terminal - supplied from the Bell circuit:
Operating Voltage
Third wire for 'AS2220 / T3 Evacuation' tone control.
- 0V on Alert terminal for the 'AS2220' tone.
Potentiometer to adjust sound output level – range = 20dB.
PS1-T3
45deg
0deg
H x W x D (mm) - depth above flush-box.
98dBA
9.5Vdc to 30Vdc
0.4µA
9mA average, 25mA peak
14mA average, 28mA peak
PS1-T3
Mounted in Wall
1
0312-PS1-T3 Sounder Issue 1.2, 200902
(@24Vdc)
(@24Vdc)
(@24Vdc)
(@24Vdc)
PS1-T3 Terminal:
Connector Layout
+
-
Alert
Bells