Base Unit Dimensions - Bryant 574B User Manual

Single-packaged gas heating/electric cooling units
Table of Contents

Advertisement

REQ'D CLEARANCES FOR OPERATION AND SERVICING. in. (mm)
Evaporator coil access side . . . . . . . . . . . . . . . . . . 36 (914)
Power entry side (except for NEC requirements) . . . . . . . . . 36 (914)
Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . 48 (1219)
Side opposite ducts
. . . . . . . . . . . . . . . . . . . . . 36 (914)
Duct panel . . . . . . . . . . . . . . . . . . . . . . . . 12 (304.8)*
*Minimum distances: If unit is placed less than 12 in. (304.8 mm) from wall
system, then the system performance may be compromised.
LEGEND
CG - Center of Gravity
COND - Condenser
EVAP - Evaporator
NEC - National Electrical Code
REQ'D - Required
Note: Dimensions are in in. (mm)
UNIT
CHARACTERISTICS
574B024040
574B030040/060
574B036060/090
BASE UNIT DIMENSIONS — 574B024-036
UNIT WEIGHT
ELECTRICAL
lb.
208/230-1-60
350
208/230-1-60
208/230-1-60
388
208/230-3-60
REQ'D CLEARANCES TO COMBUSTIBLE MAT'L. in. (mm)
Top of unit . . . . . . . . . . . . . . . . . . . . . . . . . 14 (355.6)
Duct side of unit . . . . . . . . . . . . . . . . . . . . . . . 2 (50.8)
Side opposite ducts . . . . . . . . . . . . . . . . . . . . . 14 (355.6)
Bottom of unit . . . . . . . . . . . . . . . . . . . . . . . 0.50 (12.7)
Flue panel . . . . . . . . . . . . . . . . . . . . . . . . . 36 (914.4)
NEC REQ'D CLEARANCES. in. (mm)
Between units, power entry side
Unit and ungrounded surfaces, power entry side . . . . . . . . . 36 (914)
Unit and block or concrete walls and other grounded
surfaces, control box side
UNIT HEIGHT
IN. [MM]
"A"
kg.
159
39.02 [991.1]
176
41.02 [1041.9]
—9—
. . . . . . . . . . . . . . 42 (1066.8)
. . . . . . . . . . . . . . . . . 42 (1066.8)
CENTER OF GRAVITY
IN. [MM]
X
Y
20 [508]
19.3 [489]
17.6 [447]
20 [508]
14 [355.6]
13 [330.2]
Z