Directional Unit; Current Polarization; Potential Polarization; Instantaneous Unit - GE IBCG51M A Series Instructions Manual

Ground directional overcurrent relays
Hide thumbs Also See for IBCG51M A Series:
Table of Contents

Advertisement

Current Polarization

a. Connect per Fig. 24 of TEST CONNECTIONS.
l
coil if applied too frequently or for too long a period of time.

Potential Polarization

a. Connect per Fig. 25 of TEST CONNECTIONS.
b..With V set for five volts at terminals 9 to 10, the unit should close its contacts
between 0.75-1.75 amps.

INSTANTANEOUS UNIT

Make sure that the instantaneous unit is in the correct range in which it is to
operate.
See the internal connections diagram and Table 6.
Whenever possible,
continuous rating.
The instantaneous unit has an adjustable core located at the top of the unit. T
the instantaneous unit to a desired pickup, loosen the locknut and adjust the core.
Turning the core clockwise decreases the pickup, turning the core counterclockwise
increases the pickup.
necessary to repeat this operation, until the desired pickup value is obtained. Once
the desired pickup value is reached, tighten the locknut.
CAUTION:
instantaneous unit.
the instantaneous unit.
The range of the instantaneous unit (see Table 6) must be obtained between a core
position of l/8 of a turn of full clockwise, and 20 turns counterclockwise from the
full clockwise position.
The location should be clean and dry, free fran dust and excessive vibration and
well lighted to facilitate inspection and testing.
MOUNTING
The relay should be mounted on a vertical surface. The outline and panel drilling
diagram is shown in Fig. 26.
*Indicates Revision
the higher range since the higher range has a higher
use
Bring up the current slowly until the unit picks up.
Refer to Table 6 for the continuous and one second ratings of the
Do not exceed these ratings when applying current to
6EK-49822
I N S T A L L A T I O N
17