Space-Heating Appliance In Thousands Of Btuh Per Hour - Carrier 58SP0A Installation, Start-Up, Operating And Service And Maintenance Instructions

Hide thumbs Also See for 58SP0A:
Table of Contents

Advertisement

58SP0A/58SP1A: Installation, Start–Up, Operating and Service and Maintenance Instructions
CHIMNEY INSPECTION CHART
For additional requirements refer to the National Fuel Gas Code NFPA 54/ANSI Z223.1 and ANSI/NFPA 211
Chimneys, Fireplaces, Vents, and Solid Fuel Burning Appliances
Crown
Rebuild
condition:
Yes
crown.
Missing mortar
or brick?
No
Is chimney
No
property lined with
clay tile liner?
Yes
Repair
Is
No
liner and top
liner or top seal
seal in good
or reline chimney as
necessary.
condition?
Yes
Repair
Debris
Mortar
in cleanout?
Yes
Mortar, tile, metal vent,
or tile
fuel oil residue?
debris?
No
Remove metal vent
No
or liner.
Clay
Yes
tile misalignment,
missing sections,
gaps?
No
No
Is chimney
Condensate
lined with properly
drainage at bottom
sized, listed liner or
of chimney?
Type-B vent?
Yes
No
Yes
Chimney
Is chimney
exposed to
to be dedicated to
outdoors below
a single
roof line?
Yes
furnace?
No
Chimney is
acceptable for use.
Fig. 29 – Chimney Inspection Chart
Masonry Chimney Requirement
NOTE: These furnaces are CSA design-certified for use in exterior
tile-lined masonry chimneys with a factory accessory Chimney Adapter
Kit. Refer to the furnace rating plate for correct kit usage. The Chimney
Adapter Kits are for use with ONLY furnaces having a Chimney Adapter
Kit number marked on the furnace rating plate.
If a clay tile-lined masonry chimney is being used and it is exposed to
the outdoors below the roof line, relining might be required. Chimneys
shall conform to the Standard for Chimneys, Fireplaces, Vents, and Solid
Fuel Burning Appliances ANSI/NFPA 211 in the United States and must
be in good condition.
U.S.A. - Refer to Sections 13.1.8 and 13.2.20 of the NFPA 54/ANSI
Z223.1 or the authority having jurisdiction to determine whether relining
is required. If relining is required, use a properly sized listed metal liner,
Type-B vent, or a listed alternative venting design.
NOTE: See the NFPA 54/ANSI Z223.1 13.1.9 and 13.2.20 regarding
alternative venting design and the exception, which cover installations
such as our Chimney Adapter Kits which are listed for use with these
furnaces. See Product Data Sheet for accessory listing.
The Chimney Adapter Kit is a listed alternative venting system for these
furnaces. See the kit instructions for complete details.
This furnace is permitted to be vented into a clay tile-lined masonry
chimney that is exposed to the outdoors below the roof line, provided:
1. Vent connector is Type-B double-wall, and
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Reline
Yes
Remove mortar
and tile debris
Consult
Part B of
Not Suitable
chimney adapter venting
instructions for
application
suitability.
Line chimney with property
Suitable
sized, listed flexible metal
liner or Type-B vent per
Yes
NFGC Vent
Sizing Tables and liner or
Install chimney
vent manufacturer's
adapter per
Installation instructions.
instructions.
Not Suitable
Consult
Part C of
No
Suitable
chimney adapter venting
instructions for
application
suitability
Install chimney
adapter per
instructions.
2. This furnace is common vented with at least 1 draft hood equipped
appliance, and
3. The combined appliance input rating is less than the maximum
capacity given in
4. The input rating of each space heating appliance is greater than the
minimum input rating given in
Design Temperature. Chimneys having internal areas greater than
38 sq. in. (24516 sq. mm) require furnace input ratings greater than
the input ratings of these furnaces. See footnote at bottom of
Table
6, and
5. The authority having jurisdiction approves.
Table 6 – Minimum Allowable Input Rating of

Space-Heating Appliance in Thousands of BTUh per Hour

VENT HEIGHT
FT. (M)
Local 99% Winter Design Temperature: 17 to 26 degrees F
6
8
10
15
20
30
Local 99% Winter Design Temperature: 5 to 16 degrees F*
6
8
10
15
20
30
Local 99% Winter Design Temperature: -10 to 4 degrees F*
6
A10133
8
10
15
20
30
Local 99% Winter Design Temperature: -11 degrees F or
Not recommended for any vent configuration.
*The 99.6% heating (db) temperatures found in the 1997 or 2001 ASHRAE Fundamentals
Handbook, Climatic Design Information chapter,
or the 2005 ASHRAE Fundamentals handbook, Climatic Design Information chapter, and the
CD-ROM included with the 2005 ASHRAE Fundamentals Handbook.
If all of these conditions cannot be met, an alternative venting design
shall be used, such as the listed chimney adapter kit with a furnace listed
for use with the kit, a listed chimney-lining system, or a Type-B common
vent.
Inspections before the sale and at the time of installation will determine
the acceptability of the chimney or the need for repair and/or (re)lining.
Refer to the
Fig. 29
to perform a chimney inspection. If the inspection of
a previously used tile-lined chimney:
a. Shows signs of vent gas condensation, the chimney should be
relined in accordance with local codes and the authority having
jurisdiction. The chimney should be relined with a listed metal
liner, Type-B vent, or a listed chimney adapter kit shall be used to
reduce condensation. If a condensate drain is required by local
code, refer to the NFPA 54/ANSI Z223.1, Section 12.10 for
additional information on condensate drains.
20
Table
7, and
Table 6
for the local 99% Winter
INTERNAL AREA OF CHIMNEY
SQ. IN. (SQ. MM)
12
19
28
(7741)
(12258)
18064)
0
55
99
52
74
111
NR
90
125
NR
NR
167
NR
NR
212
NR
NR
NR
NR
78
121
NR
94
135
NR
111
149
NR
NR
193
NR
NR
NR
NR
NR
NR
NR
NR
145
NR
NR
159
NR
NR
175
NR
NR
NR
NR
NR
NR
NR
NR
NR
lower
Table
1A (United States) and 2A (Canada)
38
(24516)
141
154
169
212
258
362
166
182
198
247
293
377
196
213
231
283
333
NR

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

58sp1a

Table of Contents