1- Set thermostat to occupied mode if the feature is avail
able. Make sure jumper is in place between TB1 termi
nals R and OC if using a thermostat which does not
have the feature.
2- Rotate MIN POS SET potentiometer to approximate
desired fresh air percentage.
Note - Damper minimum position can be set lower than tra
ditional minimum air requirements when an IAQ sensor is
specified. Dampers will open to DCV MAX setting (if CO2 is
above setpoint) to meet traditional ventilation require
ments.
3- Measure outdoor air temperature. Mark the point on
the bottom line of chart 1 and label the point "A" (40_F,
4_C shown).
4- Measure return air temperature. Mark that point on the
top line of chart 1 and label the point "B" (74_F, 23_C
shown).
5- Measure mixed air (outdoor and return air) tempera
ture. Mark that point on the top line of chart 1 and label
point "C" (70_F, 21_C shown).
6- Draw a straight line between points A and B.
7- Draw a vertical line through point C.
_F
-20
_C
-29
0
10
20
30
40
50
60
70
80
90
100
_F
-20
_C
-29
CHART 1
CALCULATE MINIMUM FRESH AIR PERCENTAGE
MIXED AND RETURN AIR TEMPERATURE
-10
0
10
20
30
40
-23
-18
-12
-7
-1
A
-10
0
10
20
30
40
-23
-18
-12
-7
-1
OUTDOOR AIR TEMPERATURE
8- Draw a horizontal line where the two lines meet. Read
the percent of fresh air intake on the side.
9- If fresh air percentage is less than desired, adjust MIN
POS SET potentiometer higher. If fresh air percentage
is more than desired, adjust MIN POS SET poten
tiometer lower. Repeat steps 3 through 8 until calcula
tion reads desired fresh air percentage.
DCV Set and Max Settings
Adjust settings when an optional IAQ sensor is installed.
The DCV SET potentiometer is factory-set at approxi
mately 50% of the potentiometer range. Using a standard
1-2000ppm CO
sensor, dampers will start to open when
2
the IAQ sensor reads approximately 1000ppm. Adjust
the DCV SET potentiometer to the approximate setting
specified by the controls contractor. Refer to figure 28.
The DCV MAX potentiometer is factory-set at approxi
mately 50% of the potentiometer range or 6VDC.
Dampers will open approximately half way when CO
es above setpoint. Adjust the DCV MAX potentiometer to
the approximate setting specified by the controls con
tractor. Refer to figure 28.
Note - DCV Max must be set higher than economizer mini
mum position setting for proper demand control ventilation.
50
60
70
80
90
4
10
16
21
27
32
C
B
50
60
70
80
90
4
10
16
21
27
32
Page 66