 WATER SUPPLY ‐ Water cooled models (UCG165) 
The water cooled versions require two separate inlet water supplies, one for the water sprayed for 
making the ice cubes and the other for the water cooled condenser.Connect the 3/4" male fitting of 
the water regulating valve using the flexible hose supplied with the unit to the cold water supply line 
with  regular  plumbing  fitting  and  a  shut‐off  valve  installed  in  an  accessible  position  between  the 
water supply line and the unit. 
WATER DRAIN 
The recommended drain tube is a plastic or flexible  tube  with 18 mm (3/4") I.D. runs to an open 
trapped and vented drain. When the drain is a long run, allow 3 cm pitch per meter (1/4" pitch per 
foot). A vertical open vent, at the unit drain connection, is also required for proper sump drainage. 
WATER DRAIN ‐ Water cooled models 
The water drain line from the condenser, on water cooled versions, is internally connected with the 
drain fitting of the unit. It is strongly recommended therefore to install a vertical open vent on unit 
drain line high point to ensure good draining and to direct the drain line to a trapped and vented 
floor drain receptacle. This to make sure of the proper flow of the drained water as, in case of poor 
drainage, the water ranning out from the condenser may inopportunely flow, through the unit drain 
tubing, into the ice storage bin. 
NOTE. The water supply and the water drain must be 
installed to conform with the local code. In some case a 
licensed plumber and/ or a plumbing permit is required. 
F.
FINAL CHECK LIST 
1. Is the unit in a room where the ambient temperatures are within a minimum of 50˚F (10˚C)
even in winter months? 
2. Is there at least a 6" (15cm) clearance around the unit for proper air circulation?
3. Is the unit level? (IMPORTANT)
4. Have all the electrical and plumbing connections been made, and is the water supply shut‐off
valve open?
5. Has the voltage been tested and checked against the data plate rating?
6. Has the water supply pressure been checked to ensure a water pressure of at least 14 psi (1
bar)?
7. Check all refrigerant lines and conduit lines to guard against vibrations and possible failure.
8. Have the bolts holding the compressor down been checked to ensure that the compressor is
snugly fitted onto the mounting pads?
9. Have the bin liner and cabinet been wiped clean?
10. Has the owner/user been given the Installation and Service Manual and been instructed on
the importance of periodic maintenance checks?
11. Has the unit been registered for warranty?  Check for correct model and serial number against
the serial plate.
UCG GOURMET SERIES UNDERCOUNTER 
pg. 5 