6.3.5.4 Positive Alarm Sequence (PAS) Setup
Entering 4 in the screen of Fig. 6-24 will enter the screen for setting up pre-alarm screen, as
shown in Fig. 6-28.
If the panel is set to PAS mode enabled,
On receiving the first fire alarm from a detector, PRE-ALARM LED will illuminate. The
FDCIE generates fire alarm sound, and starts 15-second delay. The LCD displays
pre-alarm message, indicating the position of the alarm and the remaining delay time.
During the 15-second delay time, if SILENCE BUZZER is pressed, the alarm sound will
stop, and the delay time will be increased by PAS DELAY (0-180s) setup.
After the delay of any stage expires, the pre-alarm will change to fire alarm and fire
protection devices in the system will be started.
During any stage of delay, if there is another detector of the same zone or any manual call
point in the system alarms, the delay will be stopped, the pre-alarm will be changed to fire
alarm, and fire protection devices in the system will be started.
During the delay time, pressing RESET will clear the pre-alarm and PAS delay.
6.3.5.5 Manual Start of Loop Device
Entering "5" in the screen of Fig. 6-24 will enter the screen for manual start of a loop devices, as
shown in Fig. 6-29. The FDCIE provides two modes, starting a single device and starting
multiple devices. The method of operation and the use of "*" is the same as disablement.
*PAS Mode*
1 Disable
2 Enable
Fig. 6-28
Start-up
Z000 C000 T00 NoDefine
Fig. 6-29