PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual CONTENTS Installation Precautions..................... 1 Preface AS 7240 Information..................2 Chapter 1 Product Introduction ................3 Chapter 2 Technical Specifications ................4 2.1 Operating Voltage ....................4 2.2 Standby Batteries....................4 2.3 Communication Loop Parameters ..............
Page 3
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual 4.7 Field Device Commission ................. 21 Chapter 5 Display and Disposal of System Information ........22 5.1 Normal Information ................... 22 5.2 Fire Alarm ......................22 5.2.1 Fire Alarm Screen ................. 22 5.2.2...
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual Installation Precautions Adherence to the following will aid in problem-free installation with long-term reliability: Do not attempt to install, service, or operate this unit until this manual is read and ...
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual Preface AS 7240 Information PFS200-2 Intelligent Fire Alarm Control Panel (FACP) complies with the AS 7240 requirements of AS 7240.2 AS 7240.4. In addition to the basic √ requirements of these standards, the panel conforms to the following optional requirements.
Maximum two Class A loops. The first loop can have up to 235 addressable devices, and the second up to 242 devices. It is compatible with a series of addressable FlameStop products, which are intelligent sounder strobe (PXI-9403) complying with 7240.3, rate of rise and fixed temperature heat detector (PHI-9103) complying with 7240.5, photoelectric smoke detector (PHI-9102)
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual And all LPCB approved Fire cables Recommended Cable Length ≤1000m 2.3.2 RS232 Communication Loop RS232 communication loop is connected with a PC for running GMC2.0 Graphic Monitor Center (GMC) system PC through a DB9 port.
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual Output Current: 0mA~500mA End of Line Resistor: 4.7kΩ 2.5.3 SOUNDER CIRCUIT OUTPUT (+, -) Output Voltage: 21VDC ~27VDC Output Current: 0mA~500mA End of Line Resistor: 4.7kΩ...
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual Chapter 3 Construction and Components 3.1 Appearance and Internal Construction PFS200-2 FACP is flush-mounted. Its appearance and internal structure are shown in Fig. 3-1 and 3-2. COMMON POWER OPERATING FIRE...
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual The display area consists of clock, LCD, LED and keypad, which are shown in Fig. 3-3. FAULT Fig. 3-3 3.1.2 Description of LEDs FIRE: Red. It illuminates when the FACP detects an alarm condition of connected detectors.
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual PRE-ALARM: Red. It illuminates when there is pre-alarm message. SEVERAL ALARMS:Red. It illuminates when there is more than one alarm exist. SOUNDER FLT/DIS: Yellow. It flashes when any loop sounder is in fault. It ...
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual through network. This key requires operator password. TAB: For shifting to display different messages or moving the cursor when entering text. MODE: Pressing this key can enter setup screen to set contrast, message display mode, printing mode, pre-alarm mode, and manual start or stop mode.
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual fault conditions are cleared or the FACP is reset. The key of a zone is used to activate/silence sounder strobes in the zone. 3.1.4.2 Device Operation Command LED: Red. It illuminates when start command is given and goes out ...
Page 15
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual addressable devices. The construction of the loop board is shown in Fig. 3-5. Fig. 3-5 24VDC power input. Communication port XS3, 20P data cable, connecting to the main board. Class A output, wiring method is the same as that of Class A detection loop on loop interface board.
A series of manual call points (such as PXI-9202) can be connected to the loop of PFS200-2. When fire is confirmed manually, pressing the glass on the MCP, alarm signal can be sent to the FACP. After receiving the alarm signal, the FACP will show the number and location of the MCP, and sound alarm.
Addressable sounder strobe is a kind of audible/ visual alarm device installed in the protected area, which can be activated by the FACP at the fire control center or by manual call points. A series of FlameStop addressable sounder strobes (such as PXI-9403) can be connected to the loop of PFS200-2.
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual Chapter 4 Installation The steps below are guidance for installation of the FACP. Check if you have received all items ordered. Install the cabinet. Power up the FACP and carry out start-up inspection.
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual Installation Holes Wiring Holes Fig. 4-1 4.3 Start-up Check After installation, apply power to it as shown in Fig. 4-2. Turn on the main and standby power supply in the cabinet and check if the FACP can self-test. The procedures are as follows.
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual Fig. 4-2a 4.4.2 Connection of Batteries Refer to the Standby Battery Calculations section for the size of the batteries required for a particular installation. Connect the batteries according to Fig. 4-2b and then connect with the battery terminal...
Page 21
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual Description: CLASS CHANGE (XT3): Shorting this terminal can make SOUNDER CIRCUIT OUTPUT (XT7) output. FAULT OUTPUT (XT8): Fault relay is closed in normal condition, and it’s disconnected in fault condition.
Page 22
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual Diode Diode End-of-line SOUNDER CIRCUIT Resistor 4.7kΩ Sounder Sounder OUTPUT (XT7) Fig. 4-4 A 4.7kΩ resistor is connected at the SOUNDER CIRCUIT OUTPUT (XT7) as factory default. Please remove it and keep it well before connection. Connect the loop in correct polarity and add the resistor to the end of the line.
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual 4.4.3.4 Connection of Class A Loop A Class A loop is shown in Fig. 4-7. Loop LOOP OUT Addressable Isolator (XT4) Field Devices Addressable Loop LOOP IN Field Devices Isolator (XT2) Fig.
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual FACP will register the devices automatically. Please check if the number of devices, programming, and operation state is in compliance with the project design and remove any problems. 4.6 Device Definition Please define devices and C&E equations by the software...
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual Chapter 5 Display and Disposal of System Information PFS200-2 can be started after installation according to description in Chapter 4. Turn on the power supply, and main and standby power switch on the FACP, the FACP executes self-test and enter normal standby state.
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual 001 0f 003 !FIRE! 05:25 Zone:001-Zone 1 002/003 Device-30 ------------------------------------- Last !Fire! Zone:003 Zone 3 Device-061 Fig. 5-3 001 0f 003 !FIRE! 05:25 // There are fire alarms in three zones and this is the first.
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual Step 1: Evacuate the people in field. Step 2: Call the fire department. Step 3: Initiate extinguishing equipment. If it is a false alarm, please take the following measures. Step 1: Press SILENCE to stop the sound.
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual The panel can monitor fire alarm. The panel can reset automatically after the fault is removed. Field device fault: If there is trouble with one of the field devices, the panel reports ...
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual There are two kinds of fault message. One is system fault, like power fault, and loop fault. The other is field device fault, like fault with detectors and modules etc.
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual Chapter 6 Description of System Operation 6.1 Keypad 6.1.1 Keypad Functions Most of the keys have double functions. Lower mark is a character and upper mark is a command that is only activated in monitoring state. Most functional keys are controlled by password.
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual Press ENTER confirm Fig. 6-2 6.2 User Operation Instruction (No Password Requirement) 6.2.1 Changing displayed time The clock usually displays in hour and minute. In normal monitoring state, pressing ENTER, month and date are displayed. Pressing ENTER again or after a minute, hour and minute is displayed again.
Page 32
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual Browse Browse Loop1: 012 Loop2: 020 Sum :012 Loop1 L1N001 Optical Loop2 L1N002 Optical Browse L1N003 Optical Zone:01 office1 L1N004 Sounder NO.001 Optical Sensitivity:Nominal Office1 Fig. 6-4 L1N001 Optical // Loop number, device address and device type.
Page 33
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual Browse ENTER 2 Group (012)(020) ENTER Group:01(001)Sum:004 Browse Group:02(002)Sum:016 Group: 01 Sum: 004 L2N001 Sounder Browse L2N002 SM Vent Group: 01 office1 L2N003 Sounder NO.001 Sounder L2N004 SM Vent Output: Persist Office1 Fig.
Page 34
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual Browse Sum:32 N01: L02N001 Sounder N02: Zone 01 N03: L01N004 Sounder Fig. 6-8 Sum:32 // Total number of keys on ZCP N01: L02N001 Sounder // Key No. 1 is defined as a sounder of Loop 2 whose address is 001.
Page 35
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual special conditions. Event: It is the message generated by the FACP when there is fire alarm or action of device. A result is composed of the following items. 01 004 13 00...
Page 36
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual 001 of 003 Disable 12:01 Z001-L2-N004Sounder Office1 Fig. 6-11 001 of 003 Disable 12:01 //There are three disabled devices in the system and this is the first. Z001-L2-N004Sounder //The zone number, loop number, address and device type ...
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual zone. Zone Part Disabled // The zone is partially disabled. 6.2.3 Silencing the panel Pressing ACK/MUTE can stop the sound of speaker; pressing ACK/MUTE again, the FACP is still in mute state. It will only sound by priority when new event appears.
Page 38
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual *Disable/Enable* 1 Disable Devices 2 Enable Devices 3 Dis/En-able Output 4 Dis/En-able Delays 5 Delete Net Disable Fig. 6-14 6.3.4.1 Disabling a Device In the screen shown in Fig. 6-14, input number “1”, you can enter disable screen as shown in Fig.
Page 39
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual Disabling a point Loop: 1 Point: 000 Fig. 6-17 Entering 1-digit loop number (1 or 2) and 3-digit point number (any number between 1 to 242), and then pressing ENTER will disable the selected device.
Page 40
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual 6.3.4.2 Enabling Devices In the screen shown in Fig. 6-14, input number 2, you can enter device enable screen as shown in Fig. 6-20. Same as disabling devices, you can also enable all devices of a zone, a single device (single-device enable) , all loop sounders, or enable a device by user code.
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual Note: If the fire alarm is from a manual call point, then the system will output immediately despite any delay settings. 6.3.4.5 Deleting Disabled Information in Network Entering number 5 in the screen of Fig. 6-14 will enter the screen for deleting disabled information in network, as shown in Fig.
Page 42
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual shown in Fig. 6-26. *Browse Mode* 1 Zone Mode 2 Loop Mode Fig. 6-26 In this screen, choosing “1 Zone Mode” can browse system messages by zone, and choosing “2 Loop Mode” can browse by loop.
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual displays pre-alarm message, indicating the position of the alarm and the remaining delay time. During the 15-second delay time, if ACK/MUTE is pressed, the alarm sound will stop, and the delay time will be increased by PAS DELAY (0-180s) setup.
Page 44
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual Pressing TEST can enter test mode setup screen as shown in Fig. 6-31. *Test Mode* 1 Display Test 2 Each Zone In Test 3 Stop a Zone Test 4 Stop All Zone Test Fig.
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual 6.3.7.4 Exiting Test Mode for All Zones Entering 4 in the screen shown in Fig. 6-31 will enter the screen for all zones to exit test mode, as in Fig. 6-34.
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual Password Change 1. Operator Password 2. Manager Password Fig. 6-37 Entering “1” or “2” can choose the password to modify, the system enters the window in Fig. 6-38. Modify Password...
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual Input “3” on the screen in Fig. 6-35, the screen shown in Fig. 6-41 will be displayed. *NETWORK SETUP* 1. NET Local Address 2. NET Event Display Fig. 6-41 In the above screen, ...
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual *Zone Start Number* Please Input 001 Fig. 6-44 6.4.5 Customize Entering number 5 in the screen in Fig. 6-35 will enter the customize screen, as shown in Fig. 6-45. *Customize* 1.
Page 49
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual Selecting “2. C&E Outputs” on the screen of Fig. 6-46 will set Sounder A on loop interface board and F.P.E. and the zonal sounder to output by C&E. The above Default Output does not take effect.
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual 6.4.6 System Initialization Entering “6” on the screen shown in Fig. 6-35 can initialize system data. 6.4.7 Viewing Supervisory Data of Addressable Devices Entering “7” on the screen shown in Fig. 6-35 will enter the window shown in Fig. 6-49.
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual Chapter 7 Standby Battery Calculations Equation for calculating the battery capacity: Battery capacity(Ah)=I ×T ) ×T Qmax Qmin Lmax Fout In which: =0.75A, which is the quiescent current when the FACP is full-loaded;...
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual Chapter 8 Maintenance The FACP shall only be repaired by specially trained technical service personnel. Please disconnect the power before repair! 8.1 Replacing the Battery Type of battery: Sealed lead-acid battery...
Page 53
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual Table 8-2 Problems Possible Causes Solutions No indication on a. AC input fuse blown a. Replace fuse. the panel or b. Power is abnormal b. Check and replace low-voltage abnormal switch power.
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual Appendix 2 Device Type List Undefine Undefined Ionization detector R+F.Heat' Rate of rise and fixed temperature detector Optical Photoelectrical smoke detector Fix Temp Fixed temperature detector Gas Det Gas detector...
Page 56
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual WTR.CURT Solenoid valve for water curtain Gas Dump Gas start-up GasAbort Gas stop Net Unit Net unit Repeater Repeater panel Module Flash-locks valve DryPower Dry powder fire extinguisher FoamPump Foam pump...
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual Appendix 3 Operation Menu Menu BROWSE 1 Loop Devices 2 Zone Devices 3 Group Devices 4 In Test Mode Zones 5 COM Devices (Network devices) 6 Access (Displaying ZCP information) 7 Browsing C&E...
Page 58
PFS200-2 Intelligent Fire Alarm Control Panel Installation and Operation Manual SYSTEM [Manager Password Required] Time/Date Password Change Network Setup Zone Start Number Customize Initialize System Devices debug ACK/MUTE (Silencing the FACP or acknowledging a fire alarm during the first stage of PAS delay)