Instruction Manual
D103425X012
Figure 3. Typical Circuit Drawings
+
INPUT
-
DC SIGNAL: 4 TO 20 MILLIAMPS
NOTE:
1
DC RESISTANCE OF COILS
CP8401‐C
B1766‐2/IL
CAUTION
Use a lubricant (key 95, figure 7) on the case‐cover threads to prevent thread damage.

Operating Information

WARNING
Personal injury or property damage may result from fire or explosion if power is applied to the transducer with the cover
removed in a hazardous area.
If the transducer is installed in an application where explosion‐proof classification is required, perform the following steps
(prior to removal of the transducer cover) when any procedure in this section requires removal of the cover:
D Disconnect the electrical signal from the transducer.
D Remove the transducer to a non‐hazardous area.
D Perform procedures as described in this section.
D Reinstall the transducer, and ensure the cover is secured before turning on the electrical signal.

Adjustments

Adjust the filter regulator to provide the proper supply pressure to the transducer, then adjust the transducer span and
zero (see figures 4 and 5) to match the application requirements and be within specifications.
+
1
INPUT
176 OHMS
-
DC SIGNAL: 10 TO 50 MILLIAMPS
450 OHMS
+
1
90 OHMS
INPUT
500 OHMS
THERMISTOR
-
DC SIGNAL: 1 TO 9 VOLTS
ADJUST RESISTANCE ACROSS INPUT
TERMINALS TO 1300 OHMS
546NS Transducer
June 2021
500
1
OHMS
1010
OHMS
9