CATIONS
SPECIFI
General Specifications
Output Voltage
Output Voltage Imbalance
Operating Temperature
Operating Temperature – PTE020 & PTE420QT
Storage Temperature
Efficiency
Short Circuit Withstand Rating
Audible Noise – PT Models
Audible Noise – PTE Models
Audible Noise – PTE "QT" Models
Start Delay on Power Up
Electrical Specifications
Power
Model
(HP)
PT007
7.5
PT010
10
PT020
20
PT030
30
PT040
40
PT050
50
PT060
60
PT075
75
Table 1 – General Specifications
Table 2 – 240 V PT Models and Ratings
Max Steady
Output
State Output
(kVA)
Current (AAC)
10.8
26
14.9
36
26.6
64
39.5
95
54.0
130
68.6
165
78.9
190
99.8
240
Appx. equal to input voltage
-10°C (14°F) to 50°C (122°F)
-10°C (14°F) to 40°C (104°F)
-20°C (-4°F) to 60°C (140°F)
Input
Max AC
Voltage
Input
Range
Current,
(VAC)
Typical (A)
45
62
111
165
187-260
225
286
329
416
V2.0
≤2%
98.7%
10kA
80 dBA
85 dBA
75 dBA
2 sec
Standby
Full Load
Power/Energy,
Energy
Typical
(W/BTU/hr)
Typical
Preliminary
(BTU/hr)
70/239
74/252
80/273
175/597
190/648
235/802
260/887
300/1024
Loss-
479
661
1180
1752
2395
3043
3500
4427
3 |
Page