Swegon BlueBox Zeta Rev Series Installation, Use And Maintenance Manual page 31

Table of Contents

Advertisement

5.7.1.3
Display of the set point
When you press and release button
With the unit "OFF" or in standby mode, with the first press of button
to the cooling mode set point while its upper part will show the relevant value.
For units in heat pump mode, with the second press of the button, the lower display will show "SetH" that corresponds to
the heating mode set point and its upper part will show the relevant value.
If compensation is envisaged, with the second press of the button for units in cooling only mode or with the third press for
units in heat pump mode, the lower display will show "Setr" that corresponds to the real operating set point and its upper
part will show the relevant value.
With the unit running, pressing on button
5.7.1.4
Changing the set point
For units that can work in cooling mode only, the set point can be changed when they are "OFF" or in standby mode.For
units that can work in both cooling and heating modes, when they are running, it is possible to change only the set point of
the active function whereas when they are "OFF" or in stand by mode, both set points can be changed.
Press, for at least 3 seconds, button
To change the value, use buttons
The new value will be stored when you press button
We reserve the right to make changes without any prior notice.
the icons identifying the circuits go out and the working set point is displayed.
will cause only the set point regarding the current operating mode to appear.
.
and
.
or with automatic exiting from the page of the function by the control.
the lower display will show "SetC" that corresponds
Translation from original instructions
31