Fan With Variable Frequency Drive (Vfd) - Carrier 48HC D17 Series Service And Maintenance Instructions

Nominal 15 to 25 tons with puron (r-410a) refrigerant
Table of Contents

Advertisement

screw bridging the split portion of the collar. The cap
screw has a Torx T25 socket head. To tighten the locking
collar: Hold the locking collar tightly against the inner
race of the bearing and torque the cap screw to 65- - 70
in-lb (7.4- - 7.9 Nm). See Fig. 7.
Fig. 7 - - Tightening Locking Collar
STAGED AIR VOLUME (SAV) CONTROL:
2 SPEED FAN WITH VARIABLE
FREQUENCY DRIVE (VFD)
Staged Air Volume (SAV) Indoor Fan Speed
System
NOTE: The SAV option is not available on units with
®
Humidi- - MiZer
adaptive humidification system.
The SAV system utilizes a Fan Speed control board and
Variable Frequency Drive (VFD) to automatically adjust
the indoor fan motor speed in sequence with the unit's
ventilation, cooling and heating operation. Conforming to
ASHRAE 90.1 2010 Standard Section 6.4.3.10.b, during
the first stage of cooling operation the SAV system will
adjust the fan motor to provide two- - thirds (2/3) of the
design airflow rate for the unit. When the call for the
second stage of cooling is required, the SAV system will
allow the design airflow rate for the unit established
(100%). During the heating mode, the SAV system will
allow total design airflow rate (100%) operation. During
ventilation mode, the SAV system will operate the fan
motor at 2/3 speed.
LOCKING COLLAR
T-25 TORX SOCKET
HEAD CAP SCREW
C11505
Identifying Factory Option
This supplement only applies to units that meet the
criteria detailed in Table 1. If the unit does not meet that
criteria, discard this document.
Table 1 – Model- - Size / VFD Option Indicator
Position in
Model / Sizes
Model Number
48HC 17 --- 28
NOTE:
See Fig. 9 for an example of typical Model
Number Nomenclature.
Unit Installation with SAV Option
48HC Rooftop — Refer to the base unit installation
instructions for standard required operating and service
clearances.
NOTE: The Remote VFD Keypad is a field- - installed
option. It is not included as part of the Factory installed
VFD option. See "Variable Frequency Drive (VFD)
Installation, Setup and Troubleshooting Supplement" for
wiring schematics and performance
configuration. See Fig 8, for location of the (VFD) as
mounted on the various 48HC models.
Fig. 8 - - VFD Location for 48HC 15- - 27.5 Units
6
VFD FIOP
Indicator
17
G, J
charts
and
VARIABLE
FREQUENCY
DRIVE (VFD)
C11531