GAS HEATING SYSTEM

General
The heat exchanger system consists of a gas valve feeding
multiple inshot burners off a manifold. The burners fire
into matching primary tubes. The tubes exit into the
collector box, the into the induced draft fan wheel inlet.
The induced fan wheel discharges into a flue passage and
flue gases exit out a flue hood on the side of the unit. The
induced draft fan motor includes a Hall Effect sensor
circuit that confirms adequate wheel speed through the
Integrated Gas Control (IGC) board. Safety switches
include a Rollout Switch mounted at the top of the burner
compartment. A limit switch is mounted through the side
of the fan deck over the tubes. The vestibule plate faces
the tubes. See Fig. 48 and Fig. 50.
GAS
VALVE
SPARK
IGNITER
MANIFOLD PRESSURE
TAP
FLAME SENSOR
Fig. 48 - - Burner Section Details
Inducer Motor
Capacitor
Inducer Cooling Fan
Fig. 49 - - Inducer Assembly
DOWN SHOT
LIMIT SWITCH
Fig. 50 - - Limit Switch Locations
Fuel Types and Pressures
Natural Gas
The 48HC unit is factory- - equipped for use with Natural
Gas fuel at elevation under 2000 ft (610 m). See section
Orifice Replacement for information in modifying this
unit for installation at elevations above 2000 ft (610 m).
Gas line pressure entering the unit's main gas valve must
be within specified ranges. See Table 7. Adjust unit gas
regulator valve as required or consult local gas utility.
Table 7 – Natural Gas Supply Line Pressure Ranges
UNIT MODEL
48HC
Manifold pressure is factory- - adjusted for NG fuel use.
Adjust as required to obtain best flame characteristic. See
Table 8.
ROLLOUT
SWITCH
Table 8 – Natural Gas Manifold Pressure Ranges
UNIT
MODEL
48HC
Liquid Propane
Accessory packages are available for field- - installation
that will convert the 48HC unit to operate with Liquid
Propane (LP) fuels. These kits include new orifice spuds,
C10334
new springs for gas valves and a supply line low pressure
switch. See section on Orifice Replacement for details on
orifice size selections.
Fuel line pressure entering unit gas valve must remain
within specified range. See Table 9.
Table 9 – Liquid Propane Supply Line Pressure Ranges
Inducer
UNIT MODEL
Wheel
48HC
Inducer
Housing
Manifold pressure for LP fuel use must be adjusted to
specified range. See Table 10. Follow instructions in the
accessory kit to make initial readjustment.
C10335
Table 10 – Liquid Propane Manifold Pressure Ranges
UNIT MODEL
48HC
SIDE SHOT
LIMIT SWITCH
Supply Pressure Switch
The LP conversion kit includes a supply low pressure
switch. The switch contacts (from terminal C to terminal
NO [Normally Open]) will open the gas valve power
whenever the supply line pressure drops below the
setpoint. See Fig. 51 and Fig. 52. The switch,
HK02LB008, opens contacts on pressure "fall" at
7.2"0.70" w.c. Contacts close on pressure rise above
10.2" w.c. If the low pressure remains open for 15 minutes
during a call for heat, the IGC circuit will initiate a
Ignition Fault (5 flashes) lockout. Reset of the low
pressure switch is automatic on rise in supply line
pressure. Reset of the IGC requires a recycle of unit
C10336
power after the low pressure switch has closed.
42
UNIT SIZE
MIN
4.0 in. wg
All
(996 Pa)
UNIT
HIGH
LOW
SIZE
FIRE
FIRE
nameplate for range
All
3.0 in. wg
2.0 in. wg
UNIT SIZE
MIN
11.0 in. wg
All
(2740 Pa)
UNIT SIZE
HIGH FIRE
All
11.0 in. wg
MAX
13.0 in. wg
(3240 Pa)
RANGE
Reference MRT unit
ratings.
MAX
13.0 in. wg
(3240 Pa)
LOW FIRE
7.3 in. wg