Bryant 564A Installation, Start-Up And Service Instructions Manual page 14

3-phase packaged air conditioners
Table of Contents

Advertisement

UNIT 564A
V-PH-HZ
SIZE
Min
036
208/230-3-60
187
042
208/230-3-60
187
048
208/230-3-60
187
208/230-3-60
187
060
460-3-60
414
(See legend following Electrical Data charts)
LEGEND
FLA
— Full Load Amps
HACR
— Heating, Air Conditioning and Refrigeration
IFM
— Indoor-Fan Motor
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps
MOCP
— Maximum Overcurrent Protection
(fuses or HACR-type circuit breaker)
NEC
— National Electrical Code
OFM
— Outdoor-Fan Motor
RLA
— Rated Load Amps
UL
— Underwriters Laboratories
* Single-Point Wiring Connections.
† Dual-Point Wiring Connections.
NOTES:
1.
In compliance with NEC requirements for multimotor and
combination load equipment (refer to NEC Articles 430 and
440), the overcurrent protective device for the unit shall be
fuse or HACR breaker. The UL, Canada, units may be fuse
or circuit breaker.
2.
Unbalanced 3-Phase supply Voltage
Never operate a motor where a phase imbalance in supply
voltage is greater than 2%. Use the following formula to
determine the percent of voltage imbalance.
% Voltage imbalance
max voltage deviation from average voltage
= 100 x
average voltage
EXAMPLE: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
TABLE 3—ELECTRICAL DATA
VOLTAGE
COMPRESSOR
RANGE
Max
RLA
LRA
254
8.9
64.5
254
10.9
73.0
254
12.3
73.0
254
16.3
114
508
7.4
64.0
OFM
IFM
ELECTRIC HEAT
FLA
FLA
Nominal kW*
-/-
3.8/5.0
10.4/12.0
1.5
2.8
7.5/10.0
20.8/24.1
11.3/15
31.3/36.1
15.0/20.0
41.7/48.1
-/-
3.8/5.0
10.4/12.0
1.5
2.8
7.5/10
20.8/24.1
11.3/15
31.3/36.1
15.0/20.0
41.7/48.1
-/-
3.8/5.0
10.4/12.0
1.5
4.2
7.5/10
20.8/24.1
11.3/15
31.3/36.1
15.0/20.0
41.7/48.1
-/-
3.8/5.0
10.4/12
1.4
5.8
7.5/10
23.8/24.1
11.3/15
31.3/36.1
15.0/20.0
47.7/48.1
-
5
0.7
2.6
10
15
20
Average Voltage =
Determine maximum deviation from average voltage.
(AB) 457 -
452 = 5 v
(BC) 464 -
457 = 7 v
(AC) 457 -
455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact your local electric utility company
immediately.
—14—
POWER SUPPLY
FLA
MCA
MOCP
-/-
15.4/15.4
20/20
16.5/18.5
20/20
29.6/33.6
30/35
42.6/48.6
45/50
55.6/63.6
60/70†
-/-
17.9/17.9
25/25
17.9/18.5
25/25
29.6/33.6
30/35
42.6/48.6
45/50
55.6/63.6
60/70†
-/-
21.1/21.1
25/25
21.1/21.1
25/25
31.3/35.3
35/60
44.3/50.4
45/60
57.4/65.4
60/70†
-/-
27.5/27.5
35/35
27.5/27.5
35/35
33.3/37.3
35/40
46.3/52.3
50/60
59.3/67.3
60/70†
-
12.6
20
6
12.6
20
12
18.3
20
18
25.8
30
24
33.3
35
452 + 464 + 455
3
1371
=
3
= 457
7
457
= 1.53%
®
DISCONNECT SIZE
FLA
LRA
15/15
15/17
27/31
74
39/45
51/59
17/17
17/17
27/31
83
39/45
51/59
21/21
21/21
29/32
87
41/46
53/60
27/27
27/27
31/34
131
43/48
55/62
15
70
15
71
18
71
24
71
31
71