2.9.38 Setting Temperature Sensors

Temperature sensors may be connected to the...
System Temperature Ports 1, 2, 3 (if available),
Temp1 and Temp2 ports on an IB2 Interface Board,
Temp1 and Temp2 ports on an EIB Interface Board,
Temp1 through Temp8 ports of up to eight (8) SM-Temp modules, and
The input block monitoring ports on the SM-DUE modules. See also "Setting the SM-DUE Parameters (if furnished)" on page
44.
NOTE!
Only the SM DUE designated as SMDUE1 and SMDUE2 via the addressing switches can have temperature probes
connected to them.
Each port (sensor) may be set as None, Battery, or Ambient.
A temperature sensor set as an ambient temperature sensor may also be set as the sensor which displays the ambient temperature
on the Web Interface's Homepage.
A temperature sensor set as a battery temperature sensor may also be set as the temperature compensation sensor (in addition, the
temperature compensation sensor is the sensor which displays the battery temperature on the Web Interface's Battery Device Group
Status Page).
A temperature sensor set as a battery temperature sensor may also be set as the BTRM (Battery Thermal Runaway Management)
sensor (in addition, the BTRM sensor is the sensor which is used for the High Temperature Disconnect [HTD] Feature.)
Procedure
1.
Set each temperature sensor in the system to None, Battery, or Ambient.
Local Menu Navigation:
None.
Web Menu Navigation:
Settings Menu / Temp Probes Tab.
Also enter values for the temp probe temperature alarms from the Web Interface (Settings Menu / Temp Probes Tab).
2.
If desired, set a temperature sensor set as an ambient temperature sensor as the sensor which displays the ambient
temperature on the Web Interface's Homepage.
Local Menu Navigation:
None.
Web Menu Navigation:
Settings Menu / System Tab / Main Ambient Temp Sensor.
Also enter values for the ambient temperature alarms from the Web Interface (Settings Menu / System Tab).
3.
If desired, set a temperature sensor set as a battery temperature sensor as the battery temperature compensation sensor.
Local Menu Navigation:
Main Menu / Settings Icon / Batt Settings / Temp Comp / TempComp Sensor.