Daikin Rebel DPS003 Installation And Maintenance Manual page 35

Commercial packaged rooftop systems
Hide thumbs Also See for Rebel DPS003:
Table of Contents

Advertisement

DOT-ITB-21-8041-AC
Ignition Control Module for Gas Furnace
Figure 35: Typical Staged Gas Furnace Electrical Schematic with Sensor
Ignition Control Module LED Diagnostics
The following LED indicators can be used to diagnose faults associated with the staged gas furnace.
Table 19: LED Indicator and Fault Conditions
Indicator
Steady Off
Steady On
1 Flash
2 Flashes
3 Flashes
4 Flashes
5 Flashes
Figure 36: Utec 1016-400 Wiring
120/240 VAC
T'STAT
120VAC
BURNER
GAS
SYSTEM WIRING DIAGRAM
www.DaikinApplied.com
L1
INDUCER
IND
MAIN
GAS VALVE
MV
PRESSURE SWITCH
PS2
PSI
LIMIT
W
FS
R
X
24VAC
C
COM
SENSE
SPARK
FOR CONTROL WITH POST-PURGE
No power or control hardware fault
Power applied, control OK
Combustion fan motor energized, pressure switch open
Combustion fan motor off, pressure switch closed
Ignition lockout from too many trials
Ignition lockout from too many flame losses within single call for heat
Control hardware fault detected
1016-4XX
HIGH
VOLTAGE
35
FPID: 437300-3-7B-01
o
pTIonal
Fault Condition
IM 1125-6 • REBEL ROOFTOPS
g
h
as
eaT