As the Heat Pump contains electrical and rotational equipment, it is recommended that ONLY competent persons carry out any work on this type of machine
This appliance is not intended for use by persons (including children) with reduced physical,sensory or mental capabilities, or lack of
experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible
for their safety. Children should be supervised to ensure that they do not play with the appliance.
The Calorex TTW units are designed for installation in a heated room, adjacent to the poolroom.
INSTALLATION MODELS TTW30/33/55/60.
1.
Remove machine from packaging.
2.
Check both sides of wall, mark out apertures 'D' and 'E' in required location
and ensure they are level.
3.
Cut out apertures 'D' and 'E' with due consideration to structure and safety
using a suitable lintel to bridge the gap.
4.
Remove the four bolts holding the dehumidifier to the wall plate and also
the earth lead.
5.
Locate the wall plate in apertures and ensure it is level. Drill and fix using
12 'C' holes and wall plugs /screws provided. Hole size 6mm (No 10) x
60mm.
6.
Lift the dehumidifier on to wall and replace six M6 bolts ald wall plate earth
lead.
7.
Fix supplied cavity bridging pieces and air inlet/outlet grilles, ensure all joints
are sealed with silicon caulking.
'D' Aperture
TTW30/33
85 high X 520 long
TTW55/60
85 high X 980 long
Aperture D
Aperture E
'C' holes
Spot
rough wall plate fixing
holes (12 off) and drill
6mm x 60mm deep holes in wall.
Fix wall plate wi
2" x No 10
screws supplied.
Mains in
Mains in
TTW55
Condensate drain tube
TTW33
10mm bore
PLANT ROOM VIEW OF MACHINE
8.
Electrical supply to the unit must be sized according to data on serial
number label paying special attention to I.E.E. regulations latest edition
regarding the special conditions governing electrical supply to machines in
potentially damp areas. The machine should be installed in accordance with
EMC2004/108/EC.
9.
The electrical supply should be connected to the terminal block mounted
on the side of the bracket supporting the compressor. Brown/red to 'live',
blue/black to neutral and earth to the stud provided.
10. Fan mode switch can be set to cycle fan when humidistat senses demand
but should be set to continuous to promote good air circulation and reduce
condensation. Note that on models fitted with LPHW the fan(s) will start
automatically whenever there is an air heating demand. On 'X' models
fan(s) will stop during defrost cycle.
11. Locate pipe from drip tray and run away to waste, a short length of 10mm
pipe is provided which should be led into a fixed waste pipe (ensure an air
gap, tun dish).
HEALTH & SAFETY WARNING
(see guarantee). Isolate electrically before entering machine or removing panels.
'E' Aperture
110 high X 520 long
110 high X 520 long
Fit cavity bridging pieces & grilles
supplied & ensure all joints are sealed
wi
silicon caulking.
218mm
MODELS WITH L.P.H.W FITTED
12. Connect water circuit piping to 15mm stubs projecting from side of
machine as per diagram below:
13. It is recommended that isolating valves are fitted to enable isolation of the
machine in the event of service.
Complete water circuit as per diagrams overleaf.
(a) Circulating pump must be sized to take into account the design flow
rate of the machine plus the water system resistance. For Pressure drops
see data section.
Unit flow rate L/min
Unit pressure drop m head
Water flow as shown
in table.
15mm stubs
TTW33
PLANT VIEW OF MACHINE
12V REMOTE HUMIDISTAT, THERMOSTAT, & REMOTE ON/OFF
CONNECTIONS
(These options need to be specified when ordering the
dehumidifier)
REMOTE HUMIDISTAT
14. Remove link wire from mains in terminal block marked 'Remote Humidistat
and connect remote humidistat as shown below, ensure dial on internal
humidistat is set fully anti-clockwise (ie maximum dehumidifcation).
REMOTE ON/OFF
15. Remove the link from the mains in terminal block marked Remote On/Off.
and connect to a switch as shown below.
'P' MODELS WITH RESISTANCE HEATER
16. Connect remote air thermostat as shown above to mains in terminal block
marked Remote Thermostat
17. Ensure safety thermostat(s) below are set, ie push red button(s).
18. Replace front cover, turn on electrical supply and turn humidistat towards
20%. (Unless remote humidistat fitted, see note 14 above) unit fan will
start, followed 6 minutes later by the compressor.
19. It is recommended that the fan mode switch is set to continuous, as in
cycle mode the fan and heaters only run together if there is a demand for
dehumidification.
FIG 2 WIRING DIAGRAM
Remote Air Stat
(Not supplied)
Remote Humidistat
(Not supplied)
Remote On/Off
Switch
(Not supplied)
100M MAX
1mm SQ CABLE
TTW30/33
TTW55/60
5.0
5.0
1.1
1.8
Water flow as shown
in table.
15mm stubs
TTW55
REMOTE THERMOSTAT
REMOTE HUMIDISTAT
REMOTE ON/OFF
SD373351 ISSUE 12

Advertisement

loading

Summary of Contents for Calorex TTW33

  • Page 1 Children should be supervised to ensure that they do not play with the appliance. The Calorex TTW units are designed for installation in a heated room, adjacent to the poolroom. INSTALLATION MODELS TTW30/33/55/60.
  • Page 2 Safety ermostat press to reset (red button) FIG 3 MODEL TTW33(7)/& TTW33(7)/& TTW30(7)AP/& TTW55(7)/& TTW55(7)/& TTW50(7)AP/& TTW30(7)A TTW30(7)AX TTW30(7)AXP TTW60(7)A TTW60(7)AX TTW60(7)AXP Dehumidification L/hr 1.25 1.25 1.25 L/day Total Heat to Air Dehumidifier only Dehum & Resistance heater 2.89 5.55 Resistance heater only Dehum &...
  • Page 3 ELECTRICAL SUPPLY CIRCUIT INCOMING SUPPLY CAPACITY TO SUIT PUMP AND DEHUMIDIFIER DEHUMIDIFIER AUX FUSEBOARD SINGLE PHASE LOCAL ISOLATOR CAPACITY TO SUIT DEHUMIDIFIER LPHW PLUMBING SCHEMATIC 3 WAY MOTORISED VALVE CONTROLLED BY CUSTOMERS THERMOSTAT LPHW FLOW CONNECTIONS BALANCE BOILER LOCATED ON VALVE DEHUM CABINET PUMP...