Advertisement

DH150/DH300/DH600
Owner installation manual (SD208050 issue 44)

Advertisement

Table of Contents
loading

Summary of Contents for Calorex DH150

  • Page 1 DH150/DH300/DH600 Owner installation manual (SD208050 issue 44)
  • Page 2 DH150/300/600 OWNER INSTALLATION MANUAL SD208050 ISSUE 44...
  • Page 3: Table Of Contents

    7.0 INSTALLATION DRAWINGS ..........15 8.0 LOW PRESSURE HOT WATER (LPHW) HEATER BATTERY OPTION ............ 18 9.0 DH150 WITH TOP DISCHARGE BOX OPTION ....19 10.0 DH600 WITH TOP DISCHARGE BOX OPTION .... 20 11.0 ELECTRICAL CIRCUIT DIAGRAMS ....... 21 12.0 WARRANTY CONDITIONS ..........
  • Page 4: Heath And Safety Warning

    DH150/300/600 OWNER INSTALLATION MANUAL HEALTH AND SAFETY WARNING This appliance can be used by children from eight years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning the use of the appliance in a safe way and understand the hazards involved.
  • Page 5: What Are The Calorex Dehumidifiers Designed To Do

    1.0 WHAT ARE THE CALOREX DEHUMIDIFIERS DESIGNED TO DO? Models DH150, DH300 & DH600 are designed to remove moisture from the point temperature. The condensed moisture forms on the evaporator coil and is air and reject the latent heat of the dehumidification process back into the air.
  • Page 6: Ordering Procedure (Model Designation)

    Allow adequate clearance to service panels on unit; recommend 500mm minimum (see installation drawings). g. All Calorex dehumidifiers are by design as quiet as is practicable, however, due consideration should be given to siting in order to fully exploit this feature, i.e.
  • Page 7: Ducting

    In order that moisture can be removed and humidity control can be effected within the required area, it is essential that correct air movement and distribution is achieved. The Calorex unit must extract the humid air generated Fig. 2. Calorex Dehumidifier installed within space to be dehumidified, with top discharge box option fitted.
  • Page 8 The humidity sensing tube situated by the air inlet is to be encompassed by or extended to any inlet air ducting. Model DH150 - minimum free area air inlet = 0·35 m². Refer to installation drawings. Model DH300 - minimum free area air inlet = 0·57 m².
  • Page 9 For applications where the condensate cannot be run to waste due to the dehumidifier being lower than the waste pipe outlet, a condensate pump option can be supplied. (Located internally on the DH150, DH300 and DH600 models). SD208050 ISSUE 44...
  • Page 10: Electrical (Machine Wiring And Supply)

    R.C.D. (residual current device) must feed both supplies. d. IMPORTANT:- Inconsistent Electrical Supply. The following Iimits of operation list not be exceeded if Calorex dehumidifiers are to be guaranteed either in performance or warranty terms:...
  • Page 11 FIG.8. DH300/600, LOCATION OF MACHINE SUPPLY TERMINAL BLOCKS Mains supply in DH300/600 Mains Terminal Block and Ear ing Point Remove front service panel (¼ turn start fasteners) Pool pump N L1 L2 L3 interlock or flow switch SD208050 ISSUE 44...
  • Page 12: Controls And Indication Lamps

    (with the compressor), or the fan can run continuously which will promote better air circulation which again helps to d. ON/OFF SWITCH - This will only be found on DH150 models and should reduce condensation by preventing stagnant air pockets.
  • Page 13: Dehumidifier Malfunction

    Check that the electrical supply and supply fuse (or MCB) to the dehumidifier are healthy and switched on. FAULT AMBER DEFROST WHITE Check that the on/off rocker switch is "ON" (DH150 only). ON/OFF MAINS Check control MCB is on (DH300/600 three phase machines only) FAULT...
  • Page 14: Dehumidifier Technical Data Sheet

    4) Minimum air temperature 0ºC for "X" models and -15ºC for "Y" models. 5) Dantherm Ltd. reserves the right to change or modify models without prior notice. 6) R407c Global Warming Potential (GWP) 1774 *DH150 features a Control Flow fan at 2500m SD208050 ISSUE 44...
  • Page 15: Installation Drawings

    7.0 INSTALLATION DRAWINGS DH150 DEHUMIDIFIER. Service panel Top view Front outlet service panel See note at foot of page Rear view L H side DISCHARGE A/C RCU Front Optional MODELS service LIQUID ONLY panel outlet sampling point Drain Air inlet...
  • Page 16 DH150/300/600 OWNER INSTALLATION MANUAL DH150 DEHUMIDIFIER - WHEELS AND HANDLES OPTION (DH150BX ONLY) Top view outlet 1087 Rear Front view view Front Optional air service outlet panel sampling point inlet Drain NOTE:- Dimensions marked * refer to dimensions of inlet DUCT FLANGE KIT OPTION (50mm Deep).
  • Page 17 DH300 DEHUMIDIFIER. AIR OFF SERVICE PANEL *740 AIR OFF AIR INLET SERVICE PANEL SERVICE PANEL DRAIN DISPLAY CONSOLE 126‡ NOTES :- Dimensions marked * refer to dimensi ons of INLET DUCT FLANGE KIT OPTION (50mm Deep). ‡ When e condensate pump is fitted service access may be necessary. DH600 DEHUMIDIFIER.
  • Page 18: Low Pressure Hot Water (Lphw) Heater Battery Option

    DH150/300/600 OWNER INSTALLATION MANUAL 8.0 LOW PRESSURE HOT WATER (LPHW) HEATER BATTERY OPTION For use with Calorex DH150 Dehumidifier only - available from your Dantherm Ltd. Distributor. Front Water out Water in DH150 wi LPHW 580 MODEL LPHW580 Output (Water at 80ºC, Air at 30ºC)
  • Page 19: Dh150 With Top Discharge Box Option

    9.0 DH150 WITH TOP DISCHARGE BOX OPTION WITH OR WITHOUT 9KW HEATER OPTION. SD208050 ISSUE 44...
  • Page 20: Dh600 With Top Discharge Box Option

    DH150/300/600 OWNER INSTALLATION MANUAL 10.0 DH600 WITH TOP DISCHARGE BOX OPTION SD208050 ISSUE 44...
  • Page 21: Electrical Circuit Diagrams

    11.0 ELECTRICAL CIRCUIT DIAGRAMS ELECTRICAL CIRCUIT DIAGRAM DH150AX SINGLE PHASE 230V 50Hz (~1N) FUSE VALUES CONTROL DH150AX WHERE CONTACTS ARE MARKED (N/O OR N/C) ON CIRCUIT DIAGRAM, THEY ARE SHOWN IN DE-ENERGISED STATE WITH REFRIGERATION CIRCUIT FULLY CHARGED RELAY/HARD START CAP IF FITTED CONTACTOR COMPRESSOR...
  • Page 22 DH150/300/600 OWNER INSTALLATION MANUAL ELECTRICAL CIRCUIT DIAGRAM DH150BX STANDARD MACHINE THREE PHASE 400V 50Hz (~3N) Fuse Values Control DH150BX Where contacts are marked N/O or N/C on e circuit diagram, are shown in e de-energised state wi e refrigeration circuit fully charged.
  • Page 23 ELECTRICAL CIRCUIT DIAGRAM DH150BX WHEELS AND HANDLES VERSION THREE PHASE 400V 50Hz (~3N) Fuse Values Control Pump (F1) (F2) (F3) DH150BX Where contacts are marked N/O or N/C on e circuit diagram, are shown in e de-energised state wi e refrigeration circuit fully charged.
  • Page 24 DH150/300/600 OWNER INSTALLATION MANUAL ELECTRICAL CIRCUIT DIAGRAM DH300BY THREE PHASE 400V 50Hz (~3N) MCB SETTING VALUES PUMP DESCRIPTION COMPRESSOR CONTROL CONTROL VALUE 11.9 20.0 MCB CONTACTS / MCB ALARM CONTACTS / MCB AUX CONTACTS SHOWN WITH CIRCUIT BREAKER MANUALLY SWITCHED...
  • Page 25 11.0 ELECTRICAL CIRCUIT DIAGRAMS. cont’ ELECTRICAL CIRCUIT DIAGRAM DH300BL THREE PHASE 400V 50Hz (~3N) MCB SETTING VALUES PUMP DESCRIPTION COMPRESSOR CONTROL CONTROL VALUE 11.9 MCB CONTACTS / MCB ALARM CONTACTS / MCB AUX CONTACTS SHOWN WITH CIRCUIT BREAKER MANUALLY SWITCHED TO THE ON CONDITION ALL OTHER CONTACTS SHOWN IN DE-ENERGISED STATE BUT WITH REFRIGERATION CIRCUIT FULLY CHARGED WHERE CONTACTS ARE MARKED (N/O) OR (N/C) ON CIRCUIT DIAGRAM ABOVE CONDITIONS APPLY CONDENSATE PUMP/...
  • Page 26 DH150/300/600 OWNER INSTALLATION MANUAL ELECTRICAL CIRCUIT DIAGRAM DH600BY THREE PHASE 400V 50Hz (~3N) ELECTRICAL CIRCUIT DIAGRAM MCB CONTACTS / MCB ALARM CONTACTS / MCB AUX CONTACTS SHOWN WITH CIRCUIT BREAKER MANUALLY SWITCHED TO THE ON CONDITION. ALL OTHER CONTACTS SHOWN IN DE-ENERGISED STATE BUT WITH REFRIGERATION CIRCUIT FULLY CHARGED.
  • Page 27 SINGLE PHASE HEATER BOX WIRING 230V 50Hz (~1N) THERMAL CUTOUT W 0,5 W 0,5 B 2,5 B 2,5 B 2,5 (SOPAC JAEGER) TECASA DELAY TIMER HIGH LIMIT STAT BL 0,5 R 1,0 GR 1,0 CONTACTOR AIR STAT CONTACTOR & O/LOAD W/R 0,5 95 96 W/R 0,5...
  • Page 28 DH150/300/600 OWNER INSTALLATION MANUAL THREE PHASE HEATER BOX WIRING 400V 50Hz (~3N) THERMAL CUTOUT W 0,5 W 0,5 B 2,5 B 2,5 (SOPAC JAEGER) TECASA DELAY TIMER HIGH LIMIT STAT BL 0,5 R 1,0 GR 1,0 AIR STAT CONTACTOR CONTACTOR...
  • Page 29: Warranty Conditions

    12.0 WARRANTY CONDITIONS If in doubt or if advice is required please contact the Dantherm Group UK Service Department by calling 01621 856611 (option 4) or emailing service@dantherm.com The following exclusions apply to the Warranty given by Dantherm Ltd. Note: The Reply Paid Warranty Registration Card must be returned, to ensure No claims will be accepted if :- that the correct warranty is given.
  • Page 30: Machine Record Log

    DH150/300/600 OWNER INSTALLATION MANUAL 13.0 MACHINE RECORD LOG In order to comply with European F-Gas regulations, it is necessary for hermetically sealed systems with more than 6kg refrigerant to be leak tested annually. The operator of the unit is responsible for seeing that the test is carried out.
  • Page 31 SD208050 ISSUE 44...
  • Page 32 Dantherm Ltd. Unit 12, Galliford Road Maldon CM9 4XD United Kingdom Calorex is part of the +44 (0)1621 856611 sales.uk@dantherm.com SD208050 ISSUE 44...

This manual is also suitable for:

Dh300Dh600

Table of Contents