Step
3
Remove the sheets of
putty and shield plate.
4
Remove the terminal
cover and the
protection bushing.
5
Disconnect the
compressor lead wires
and detach the
overload protector.
6
Heat up the 4 brazed
parts of the four way
valve in the order of (a)
(b) (c) (d).
7
Remove the four way
valve.
Removal Procedure
Procedure
Shield plate
Terminal cover
Protection
bushing
Overload protector
(d)
(c)
(b)
Four Way Valve / Electronic Expansion Valve
(R19636)
U (red)
W (blue)
V (yellow)
(R21601)
Four way valve
(a)
(R19638)
Points
Be careful so as not to burn
the compressor terminals or
the name plate.