Troubleshooting - ReddyHeater BWH10NLMC-2 Owner's Operation And Installation Manual

Vent-free gas wall heater blue flame model
Table of Contents

Advertisement

Available languages

Available languages

WARNING: If you smell gas:
• Shut off gas supply.
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your
building.
• Immediately call your gas supplier from a neighbor's phone. Fol-
low the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
WARNING: Only a qualified service technician should service and
repair heater. Make sure that power is turned off before proceeding.
Turn off and let cool before servicing.
CAUTION: Never use a wire, needle, or similar object to clean
ODS/pilot. This can damage ODS/ pilot unit.
IMPORTANT: Operating heater where impurities in air exist may create odors. Cleaning sup-
plies, paint, paint remover, cigarette smoke, cements and glues, new carpet or textiles, etc.,
create fumes. These fumes may mix with combustion air and create odors.
Note: All troubleshooting items are listed in order of operation.
Problem
Using natural gas and
pilot will not light.
Pressure Switch
When using natural gas (NG), there is a
pressure switch that acts to turn off the gas
flow to the pilot if the inlet pressure exceeds
9.5" WC. This is to prevent the operation of
the unit on the wrong gas (propane/LP). If your
natural gas supply exceeds 9.5" WC the unit
will not operate. Either contact your gas sup-
plier to check and adjust the inlet pressure or
a qualified service technician can bypass the
pressure switch.
Before attempting to bypass the pressure
switch, make sure the type of gas being used
is correct. Check to make sure the connection
fitting is in the correct inlet on the regulator.
Refer to Connecting to Gas Supply, page 15.
Only a qualified installer should bypass the
pressure switch. Remove front panel of heater
(see page 10). Locate the gas regulator. To by-
pass the pressure switch locate the set screw
on the regulator. Use a small flat bladed screw
driver to turn the set screw counterclockwise
2 turns. This will bypass the pressure switch
function.
22

TROUBLESHOOTING

Possible Cause
Inlet pressure exceeds 9.5" WC. Bypass pressure switch. See
www.sureheat.com
Corrective Action
instructions below.
The entire gas delivery piping including con-
nections inside the heater should be leak
tested by the qualified installer. After leak
testing the qualified installer should light the
appliance. Refer to the correct flame pattern
as illustrated on page 20. All flame patterns
should be safely inside the product. If for any
reason they are not, stop use of the appliance
and call for repairs.
Pressure
Switch Set
Screw
Figure 27 - Gas Regulator Pressure
Switch (Inside Bottom of Heater Cabinet)
200311-01C