Fire Sentry Corporation Telephone: 714-694-2700 23311 La Palma Avenue Fax: 714-694-2701 Yorba Linda, California 92887 www.firesentry.com FS17X WideBand IR Multi-Spectral Infrared Electro-Optical Digital WideBand IR Sensor Radiant Energy Fire and Flame Detector Fire and Flame Detectors MODEL FS17X Installation Guide...
Three Separate Bright LEDs (Red, Yellow, Blue) for quick, easy identification of ALARM, Fault and Normal status for semiconductor clean room environments. Our Windows® based PC Software for remote FSX diagnostics and data retrieval. Designed, Manufactured, Tested, and Patented by Fire Sentry Corporation (30 years of proven fire / flame detection product excellence worldwide). Applications...
Page 12
The TL-1055X and the TL-2055X are the ONLY Test Lamps that will activate the FSX Detectors. Additionally, do not use these Test Lamps to activate other Fire Sentry Detectors such as the Models SS2 or SS4 (nor any other conventional fire and flame detectors). Do not use other Fire Sentry Test Lamps to test the FSX Detectors.
Page 13
Remember to disable the Detector outputs, as a full functional test includes activating the alarm outputs. A FSX Fire Sentry Test Lamp must be used for this test (Section 4.3). Point the Test Lamp directly at the front of the Detector (on axis as much as possible, within a distance of 1 to 25 feet). Activate the Test Lamp by pressing and holding its pushbutton.
0.7 to 1.1 microns. The Visible Band and NearBand IR are used primarily to further discriminate against non-fire false alarm sources. As with all Fire Sentry Corporation Detectors, the Model FS17X Detector senses radiant energy generated by both hydrocarbon and non-hydrocarbon fires.
2 Only one active Fault output from this group Yellow LED Location The FS17X has the following Fault (Trouble) outputs: Flashes LED Fault Cause Remedy Contact Fire Sentry Corporation to speak Yellow Self Test Fault Sensor response is out of range. with a Technical Representative.
Additionally, semi-annual or quarterly testing should be performed, using the correct Fire Sentry Test Lamp, to ensure the integrity of the entire fire protection system. (see Note in Section 2.4 and Section 4.3) Clean the FS17X Detector window: Each time the Detector is taken out of or put back into to service.
Fire Sentry Corporation assumes no obligations or liability for additions or modifications to this warranty unless made in writing and signed by an officer of Fire Sentry Corporation. Fire Sentry Corporation does not warrant the installation, maintenance or service of its Products. Fire Sentry...
Some flame detector manufacturers claim that their Detectors do not need remote testing with an external Test Lamp because their Detectors test themselves. Even though Fire Sentry Corporation Detectors also test themselves, Fire Sentry Corporation, in compliance with NFPA 72 codes, has developed portable test lamps for periodical “end-to-end”...