Fire Sentry FS19X-211-213 Installation Manual And Operating Manual

Fire and flame detectors

Advertisement

Quick Links

FS19X & FS20X WideBand IR
/ UV
TM
Multi-Spectrum Infrared / Ultraviolet Electro-Optical Multi-Spectral Digital
WideBand IR Sensor with Ultraviolet Phototube
Radiant Energy Fire and Flame Detector
FSX
TM
P
P
Fire and Flame Detectors
TM
TM
MODEL FS19X
& FS20X
Series
Installation Guide
and
Operating Manual
____________________________________________________________________________________________________________________
©
Fire Sentry Corporation
Document No. 6178-004 - Rev. G
Copyright 2011
All Rights Reserved

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the FS19X-211-213 and is the answer not in the manual?

Questions and answers

Summary of Contents for Fire Sentry FS19X-211-213

  • Page 1 WideBand IR Sensor with Ultraviolet Phototube Radiant Energy Fire and Flame Detector Fire and Flame Detectors MODEL FS19X & FS20X Series Installation Guide Operating Manual ____________________________________________________________________________________________________________________ © Fire Sentry Corporation Document No. 6178-004 - Rev. G Copyright 2011 All Rights Reserved...
  • Page 2 Sentry, COP-i, Complete Optical Path Integrity, CM1, CM1-A, DartLogic, FireLogic, Fire Signature Analysis, FireBusI, FireBusII, FirePic, FirePicII, FirePicIII, FirePix, FirePicture, FSC, Fire Sentry Corporation, Fire Sentry Corp., FSX, All FSX Nomenclature Variations (such as: FS2, FS2X, FS2X, FS3, FS3X, FS3X, FS4, FS4X, FS4X, FS5, FS5X, FS5X, FS6, FS6X, FS6X, FS7, FS7X,...
  • Page 3: Table Of Contents

    4.7 Drawings ................................20 4.7.1 Outline and Dimensions ........................20 4.7.2 Wiring and Terminal Connections ......................21 4.7.3 Detector Label Drawings ........................23 INDEX ..................................25 Fire Sentry Corporation Document No. 6178-004 - Rev. G © Copyright 2011 All Rights Reserved...
  • Page 4: Section 1: Introduction

    3. The ten (10) position Rotary switch allows selection of Figure 1-2 the analog and digital communication protocol. FS19X/FS20X Detector Puck, ( rear view Page 1 Fire Sentry Corporation Document No. 6178-004 - Rev. G © Copyright 2011 All Rights Reserved...
  • Page 5: Detector Technical Specifications

    The supply connection wiring shall be rated at least 10°C above the rated service temperature (120°C for T4 applications and 85°C for T5 applications) Page 2 Fire Sentry Corporation Document No. 6178-004 - Rev. G © Copyright 2011 All Rights Reserved...
  • Page 6: Features & Benefits

     FSC Windows® based PC Interface User can perform remote FS20X Detector diagnostics, real-time status, Real-Time Graphing (RTG), SnapShot data recording, and downloading FirePic’s with Fire Sentry’s exclusive FSIM-2 USB ® Interface Unit and easy to use Windows based PC Software.
  • Page 7: Applications

    Power Plants Product Storage Terminals Rail and Truck Loading and Unloading Terminals Silane Gas Cabinets Silane Gas Manufacturing Hydrogen Plants Hydrogen Storage General Warehouses Page 4 Fire Sentry Corporation Document No. 6178-004 - Rev. G © Copyright 2011 All Rights Reserved...
  • Page 8: Section 2: Installation

    Install an approved conduit trap or drain, if required to meet hazardous area classifications per NFPA 70: National Electrical Code, latest revision. Figure 2-1 Detector (front view) Swivel Mount Figure 2-2 Figure 2-3 Page 5 Fire Sentry Corporation Document No. 6178-004 - Rev. G © Copyright 2011 All Rights Reserved...
  • Page 9: Opening The Detector

    4. Loosen the set screw on the enclosure lid (see Figure 2-5). Figure 2-5 5. Turn counterclockwise (CCW) to unscrew the enclosure lid (see Figure 2-6). Figure 2-6 Page 6 Fire Sentry Corporation Document No. 6178-004 - Rev. G © Copyright 2011 All Rights Reserved...
  • Page 10: Detector Connections

    DC Return Contacts shown with no power applied Note: Do not attempt to open the Detector Module “puck” as this voids all warranties. Page 7 Fire Sentry Corporation Document No. 6178-004 - Rev. G © Copyright 2011 All Rights Reserved...
  • Page 11: Installation Practices

    The Detector is now ready for Power-Up. On Power-Up, the Fault Relay will change status if the Factory Default Setting is used (Section 3.2). Page 8 Fire Sentry Corporation Document No. 6178-004 - Rev. G © Copyright 2011 All Rights Reserved...
  • Page 12: Start-Up And Commissioning

    The TL1055X and the TL2055X are the only Test Lamps that will activate the FSX Detectors. Additionally, do not use these Test Lamps to activate other Fire Sentry Detectors (nor any other conventional fire and flame detectors). Do not use other Fire Sentry Test Lamps to test the FSX Detectors.
  • Page 13 2. Check the Distance: verify that the testing distance is between one (1) and twenty-five (25) feet from the FSX Detector(s). 3. Check Aiming Accuracy: verify that the proper testing technique (as described above) is followed. Page 10 Fire Sentry Corporation Document No. 6178-004 - Rev. G © Copyright 2011 All Rights Reserved...
  • Page 14: Section 3: Operation

    Built-in microprocessors use sophisticated Digital Signal Processing (DSP) to accurately distinguish radiant energy from a real fire and a false alarm source(s). Fire Sentry has developed and refined these complex proprietary and patented WideBand IR and UV algorithms for over a quarter of a century since 1981.
  • Page 15 Figure 3-3 to configure SW3. Factory Use Only Figure 3-3 SW3 Factory Use Only Ten (10) Position Rotary Switch Factory Use Only Page 12 Fire Sentry Corporation Document No. 6178-004 - Rev. G © Copyright 2011 All Rights Reserved...
  • Page 16: Normal Operation

     RS-485 ModBus Alarm Notification 1 This output is a Verified Alarm Output Figure 3-5 2 Only one active Alarm output from this group Red LED Location Page 13 Fire Sentry Corporation Document No. 6178-004 - Rev. G © Copyright 2011 All Rights Reserved...
  • Page 17: Fault Conditions

    Additionally, semi-annual or quarterly testing should be performed, using the correct Fire Sentry Test Lamp, to ensure the integrity of the entire fire protection system. The optical window (lens) of the Model FS19X/FS20X Detector should be clean in order to ensure the Detector is operating properly at all times.
  • Page 18: Section 4: Appendix

    Products shall become the property of Fire Sentry Corporation. This express limited warranty is extended by Fire Sentry Corporation to the original purchaser only and is not assignable or transferable to any other party. This is the complete warranty for the Products manufactured by Fire Sentry Corporation.
  • Page 19: Product Variations

    2 = High Temperature Applications 3 = Fast Response (0.5 Seconds) Manufacturer’s Code 2 = Standard Fire Sentry Detector – Full Window FS19X-211-213 MultiBand IR plus UV Detector, General Applications with Relays, 4-20mA Output, FireBus Aluminum Enclosure with ¾ inch NPT Conduit Entries, Class...
  • Page 20: Digital Communication Options

    Some manufacturers claim that their detectors do not need remote testing with an external Test Lamp because it tests itself. Even though Fire Sentry Detectors also perform “through the lens” self-testing and tests themselves, Fire Sentry, in compliance with NFPA 72 codes, has developed portable test lamps for periodical “end-to-end”...
  • Page 21: Additional Performance Specifications

    The optional extended temperature range FS19X/FS20X Detector will respond to a one (1) square foot n-heptane reference fire at a distance of 35 feet in 2 to 5 seconds, when the temperature exceeds 85°C. Page 18 Fire Sentry Corporation Document No. 6178-004 - Rev. G © Copyright 2011 All Rights Reserved...
  • Page 22: 4.6.3 False Alarm Immunity

    Fire at 200 feet / 60.96 meters Source at 3 feet / 91.44 centimeters Incandescent Lamp 1 foot / 30.48 centimeters Fire at 200 feet / 60.96 meters Page 19 Fire Sentry Corporation Document No. 6178-004 - Rev. G © Copyright 2011 All Rights Reserved...
  • Page 23: Drawings

    INSTALLATION GUIDE and OPERATING MANUAL Drawings 4.7.1 Outline and Dimensions Figure 4-3 Outline & Dimesional Drawing for FS19X/FS20X Figure 4-4 Outline & Dimesional Drawing for SM4 Page 20 Fire Sentry Corporation Document No. 6178-004 - Rev. G © Copyright 2011 All Rights Reserved...
  • Page 24: Wiring And Terminal Connections

    2. Set SW3 (rotary switch) to position one (1) for Source current wiring. 3. Set SW3 (rotary switch) to position zero (0) for Sink current wiring. Page 21 Fire Sentry Corporation Document No. 6178-004 - Rev. G © Copyright 2011...
  • Page 25 De-Energize and the N.O. (normally open) contacts will close. 4. EOL (End-Of-Line) device shall be installed as required and supplied by the Fire Alarm Panel. Page 22 Fire Sentry Corporation Document No. 6178-004 - Rev. G © Copyright 2011...
  • Page 26: Detector Label Drawings

    Figure 4-9 FS20X Label for Class & Division 1 and Class Hazardous Locations Figure 4-10 FS20X Label for Class , Zone 1 Hazardous Locations Page 23 Fire Sentry Corporation Document No. 6178-004 - Rev. G © Copyright 2011 All Rights Reserved...
  • Page 27 Figure 4-11 FS19X Label for Class & Division 1 and Class Hazardous Locations Figure 4-12 FS19X Label for Class , Zone 1 Hazardous Locations Page 24 Fire Sentry Corporation Document No. 6178-004 - Rev. G © Copyright 2011 All Rights Reserved...
  • Page 28: Index

    High Temperature Response ........18 Weather-proof .............. 8 Wiring and Terminal Connections ....... 21, 22 Installation Practices ..........7, 8 Yellow LED ..............14 Page 25 Fire Sentry Corporation Document No. 6178-004 - Rev. G © Copyright 2011 All Rights Reserved...
  • Page 29 Thank you for reading this data sheet. Please contact us for a quotation: Head Office (UK) Switzerland Office P.O. Box 2124 Zugerstrasse 46 Chelmsford 6314 Unterägeri Essex CM1 3UP England Switzerland Tel: +44 (0)1245 600 560 Tel: +41 41 541 5877 Fax: +44 (0)1245 600 030 Fax: +41 41 541 5878 Email:...